The battery voltage is lower than the battery
shut down level specified for this UPS unit.
A59 – Batteries
Possible causes include a blown fuse, an
disconnected
unstable battery connection or disconnection of
the battery cable.
A60 – Excessively high
The battery voltage is excessively high
battery voltage
A61 – Charger error
The charged is defective
A62 – Battery defective
Defective batteries detected
A64 – Overload
Overload in the UPS unit's output
A66 - EPO
EPO activated
A68 - Excessively high
Ambient temperature too high or ventilation
temperature
openings covered.
A69 – Fans blocked
Fans blocked
Table 7 presents the most typical problems, their possible causes and proposed
troubleshooting activities.
Table 7. Typical problems, their causes and recommended activities.
Problem
The device has not been switched on
logically.
A set of controlled outputs is off.
The UPS will not
switch on or
supply power to
the connected
Critically low battery charge level.
devices
The internal battery circuit is
disconnected.
The number of external battery modules
connected to the UPS is not defined.
Excessively short
duration of
The UPS unit's battery is discharged due
operation in back-
to recent power outage.
up (battery) mode
The battery has been used up.
The battery
Input circuit protection triggered.
operates in back-
up (battery) mode,
despite the
presence of
Mains parameters are out of the UPS
voltage in the
unit's range.
mains.
2019-11-25 11:43
EVER POWERLINE RT PLUS UPS Operating Manual
Possible cause
Technical Support, phone: +48 61 6500 400
Make sure all batteries are properly connected. If the
situation persists, contact service support.
Contact service support
Contact service support
Contact service support
To reduce the load in the output of the UPS unit,
disconnect some receivers.
Check the status of the EPO connector and the
triggering device.
If the temperature remains excessively high, the UPS
unit should be turned off. Uncover the ventilation
openings and remove any sources of heat. Wait until
the UPS unit cools down. Ensure free air circulation
around the UPS unit. Restart the UPS unit.
Check the UPS unit's fans. If the situation persists,
contact service support.
Action
Switch the UPS by pressing the ON button
on
the
control
panel
depressed for over 1 s.
Switch on a set of outputs (menu 010).
The UPS must be connected to the mains
and switched on in order to recharge the
battery.
Check the correctness of connections. If the
connections are done correctly, contact the
service support.
Use the UPS unit's menu to configure the
number of battery modules.
Recharge the battery after a prolonged
power outage.
Replace the battery.
Disconnect the less critical devices from the
UPS. Rearm the input circuit protection.
Connect the UPS to another source of
power.