Installation guidelines for the POWERLINE RT PLUS 6-10 kVA units TABLE OF CONTENTS TABLE OF CONTENTS ............................2 SAFETY REMARKS ............................3 REQUIREMENTS FOR PREPARATION OF THE POWER SUPPLY AND RECEIVER SYSTEM ..3 INSTALLATION GUIDELINES ........................5 ELECTRICAL SYSTEM ........................... 7 TECHNICAL ACCEPTANCE ..........................
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA unit SAFETY REMARKS Read and understand the safety remarks and guidelines in the (full) Instruction Manual of this UPS before attempting any switching operations. REQUIREMENTS FOR PREPARATION OF THE POWER SUPPLY AND RECEIVER SYSTEM Shipping requirements.
Page 4
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA units strength of the installation location. The base structure must prevent collapsing under the device weight. Do not cover any ventilation openings of the device. Ensure proper ventilation of the room where the batteries are installed (this also applies to units with integrated batteries).
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA unit the topology of which matches the connection diagram of the UPS (see the instruction manual for the external bypass system) for operating and maintenance purposes. The bypass system will enable servicing and maintenance of the device without power interruptions! ...
Page 6
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA units Table 1. Installation guidelines for the POWERLINE RT PLUS 6 – 10 kVA UPS. POWERLINE RT PLUS PARAMETERS / MODEL POWERLINE RT PLUS 6000 POWERLINE RT PLUS 10 000 Apparent / active power 6 kVA / 6 kW 10 kVA / 10 kW POWER SUPPLY PARAMETERS...
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA unit ELECTRICAL SYSTEM Prepare the electrical system according to the diagram shown in Fig. 1. Figure 1. Installation diagram of the POWERLINE RT PLUS 6-10 kVA UPS Installation diagram symbols: Fm, Fsb – Switch fuses, Qout, Qsb –...
Page 8
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA units CAUTION! Use LgY wires for the UPS cables. CAUTION! Follow the phase rotation order when collecting the power supply line. This applies to all components of the BYPASS switchboard and the UPS connection. ...
Installation guidelines for the POWERLINE RT PLUS 6-10 kVA unit TECHNICAL ACCEPTANCE In order to commission the installed device for operation, do the following in witness of a person authorised for technical acceptance: Measure the battery voltage. Measure the output voltage in the mains operating mode. ...