FIG. 5 CONNECTION DIAGRAM Thyro-AX 3A WITH LOAD IN OPEN
DELTA CONNECTION
X3 1 2 3

5.2 LOAD CONFIGURATION

For load connection if applicable the wiring has to be adjusted for
terminals X1 and X10. This depends on the connection option and has
to be done in accordance to the respective connection diagram, see
chapter 5.1.7 Connection diagrams.
- Star or delta connection without N: Factory setting, no changes
necessary
- Star connection with N: Changes of wiring of X1 and X10 necessary
- Open delta connection: Changes of wiring of X1 and X10 necessary
When changing the load connection is has to be adjusted via para-
meters. This setting can be done by touch display, Thyro-Tool AX soft-
ware or acyclic communication of a bus protocol.
Touch display
The general functionality of the touch display is explained in chapter 7.
Display and operational elements. If the connection option has not
previously been set up via EasyStart configuration or has not yet been
changed, the modification can be done in accordance to the following
structure:
Menu
Settings
ActVal
AO 2
Events
AO 3
Settings
Hardware
ReadSet
Operating
Code
Regulator
Thyro-Tool AX
Load configuration can be found under the same parameter name
(symbol: LoadConf). The modification has to be saved in the unit for
permanent usage.
Settings -> Hardware -> LoadConf -> Star connection with N (only
Thyro-AX 3A version)
Star or delta connection without
N (factory setting)
Open delta connection
31