Scope Of Supply; Storage; Assembly; Connection - Advanced Energy THYRO-AX Manual

Thyristor power controller
Hide thumbs Also See for THYRO-AX:
Table of Contents

Advertisement

Available languages

Available languages

10

1.5 SCOPE OF SUPPLY

The supply consists of the following parts:
• Thyro-AX
• Accessory bag with screw/push terminals
• Operating instructions
• Safety note stickers

1.6 STORAGE

The devices may be stored originally OEM packaged in rooms, which
are dry and ventilated.
• permissible ambient temperature: -25 °C to +55 °C
• permissible relative air humidity: max. 85%
For longer storage durations, the devices should be contained in airtight
plastic skins with the addition of commercially available drying agents.

1.7 ASSEMBLY

• If stored in cold environments it must be ensured that the device is
absolutely dry before commissioning. Therefore allow at least 2 hours
acclimatization time before commissioning.
• Ensure sufficient ventilation and de-aeration of the cabinet if mounted
in a cabinet.
• Observe minimum spacing.
• Ensure that the device cannot be heated up by heat sources below it.
(see Technical data).
• Ground the device in accordance with the local regulations.
• Connect the device in accordance with the connection diagrams.
For further details see the chapter „Installation".

1.8 CONNECTION

Before connection, the indicated voltage on the type plate is to be
compared with the mains voltage to make sure they match. The electrical
connection is made at the points labelled on the Thyro-AX.

1.9 MAINTENANCE, SERVICE, FAULTS

The symbols used in the following are explained in the chapter on
safety requirements.
In order to avoid damage to personnel or property the user must note
the following points before all work:
CAUTION
In the case of smoke or smell development, as well as in the case of
fire, the power controller shall immediately be disconnected from the
power supply.
CAUTION
For maintenance and repair works the power controller must be dis-
connected from all external voltage sources and safeguarded against it
being switched on again. After switching off wait at least two minutes
for the snubber capacitors to discharge. The absence of voltage is to
be ascertained using appropriate measurement instruments. The device
is to be grounded and short-circuited. Adjacent components under
voltage are to be covered or separated off. These activities may only be
carried out by an electrically qualified person. The local electro-techni-
cal regulations are to be adhered to.
CAUTION
The thyristor controller contains voltages which are hazardous. Repairs
are strictly only to be carried out by qualified and trained maintenance
personnel.
CAUTION
Hazard of electric shocks. Even after the separation from the mains,
capacitors can still contain dangerously high levels of energy.
CAUTION
Hazard of electric shocks. Even with a non-activated thyristor cont-
roller the load circuit is not separated from the mains by the thyristor
controller.
ATTENTION
Different power components are screwed in place with exact torques
according to their function. For safety reasons repairs to power com-
ponents are to be carried out by Advanced Energy Industries GmbH.
Repairs by personnel of the operator require a written confirmation of
the manufacturer.