Easystart - Advanced Energy THYRO-AX Manual

Thyristor power controller
Hide thumbs Also See for THYRO-AX:
Table of Contents

Advertisement

Available languages

Available languages

56
DESCRIPTION OF
FAULT
THYRISTOR SHORT CIRCUIT
U-MEASURING RANGE
IS EXCEEDED
I-MEASURING RANGE
IS EXCEEDED
NEGATIVE POWER
* = cannot be deactivated
** = default setting of fault signaling relay K1: closed circuit principle
DESCRIPTION OF
STATUS
U LIMIT
I LIMIT
P LIMIT
IPEAK LIMIT
ALPHA IS RESTRICTED
TS IS RESTRICTED
MAXIMUM CONTROLLER
OUTPUT IS REACHED
* = cannot be deactivated
** = default setting of fault signaling relay K1: closed circuit principle
DESCRIPTION OF
MONITORING
U
MIN
MAINS
U
MAX
MAINS
U
MIN
LOAD
U
MAX
LOAD
I
MIN
LOAD
I
MAX
LOAD
P
MIN
LOAD
P
MAX
LOAD
R
MIN
LOAD
R
MAX
LOAD
I
MAX
PEAK
* = cannot be deactivated
** = default setting of fault signaling relay K1: closed circuit principle
TAB. 8 ACKNOWLEDGMENT
THYRO-TOOL AX
MESSAGE
ACKNOWLEDGE VIA
MESSAGE
ON DISPLAY
LCD DISPLAY
THYRISTOR SHORT
THYRISTOR
X
CIRCUIT
U MEASURING
U RANGE
X
RANGE EXCEEDED
I MEASURING
I RANGE
X
RANGE EXCEEDED
NEGATIVE POWER
NEG POWER
X
THYRO-TOOL AX
MESSAGE
ACKNOWLEDGE VIA
MESSAGE
ON DISPLAY
LCD DISPLAY
U LIMIT
U LIMIT
X
I LIMIT
I LIMIT
X
P LIMIT
P LIMIT
X
I PEAK LIMIT
IPEAKLIMIT
X
ALPHA RESTRICTED
ALPHA
X
SWITCH ON TIME
TS
X
RESTRICTED
MAXIMUM OUTPUT
MAXCONTROL
X
REACHED
THYRO-TOOL AX
MESSAGE
ACKNOWLEDGE VIA
MESSAGE
ON DISPLAY
LCD DISPLAY
U MAIN < MINIMUM
UN MIN
X
U MAIN > MAXIMUM
UN MAX
X
U < MINIMUM
UL MIN
X
U > MAXIMUM
UL MAX
X
I < MINIMUM
IL MIN
X
I > MAXIMUM
IL MAX
X
P < MINIMUM
PL MIN
X
P > MAXIMUM
PL MAX
X
R < MINIMUM
RL MIN
X
R > MAXIMUM
RL MAX
X
I PEAK > MAXIMUM
I_PEAK MAX
X

7.4 EASYSTART

In the case of the initial start of the device the managed parameteriza-
tion EasyStart is called up with the help of which the fundamental pa-
rameterization is configured. The following screens are depicted in the
displayed sequences. The ESC button calls up the previous page and as
such allows alterations to be made to settings already inputted.
During the configuration with EasyStart the pulse inhibition is active
and prevents power being emitted at the load side.
Start screen:
The parameterization of the fundamental values starts
with the button Yes. With No EasyStart is aborted, in
order, for example, to transfer an already saved parameter
file to the device using the Thyro-Tool AX.
Load factory settings:
The button Yes sets the Thyro-AX back to its default
settings. When pressing the button No, the Thyro-AX
continues EasyStart feature on basis of its current settings.
If EasyStart has been started once, it will request first the
default settings before EasyStart start screen appears.
Load type:
Here, adjustment to a purely ohmic load or an inductive
load, as occurs in transformers, is possible. As such in
case of a purely ohmic load the power controller can clock
more quickly with the R-Load setting and provides a larger
dynamic on the output side. Configuring a transformer
load with RL-Load causes an angle of the first half wave
(Alpha 1
st
) each time it switches through and an optimi-
zation of the necessary time intervals for the controlled
magnetization of the transformer coils.
57