Advanced Energy ARTESYN Power Management Controller Manual

Advanced Energy ARTESYN Power Management Controller Manual

For 1ou ocp power supply units

Advertisement

Quick Links

ARTESYN
Power Management Controller
For 1OU OCP Power Supply Units (PSU)
Advanced Energy's Artesyn Power Management Controller
(PMC) is a hot-pluggable controller in the shelf that
monitors and facilitates the power supply units through
a 10/100/1000MB Base-T Ethernet port and can be
connected directly to the rack switch.
The PMC communicates with PSUs in the shelf through the
backplane connector. The front connector provides one
Ethernet port and one RS232 port for debugging.
The PMC is connected via Ethernet to a switch (normally the
top of rack controller/switch) and up to 6 PSUs are monitored.
AT A GLANCE
Typical Application
Open Compute Project
Input Voltage
48 VDC
Connector
4 x RJ45 Connectors
©2023 Advanced Energy Industries, Inc.

Advertisement

Table of Contents
loading

Summary of Contents for Advanced Energy ARTESYN Power Management Controller

  • Page 1 ARTESYN Power Management Controller For 1OU OCP Power Supply Units (PSU) Advanced Energy's Artesyn Power Management Controller AT A GLANCE (PMC) is a hot-pluggable controller in the shelf that monitors and facilitates the power supply units through Typical Application a 10/100/1000MB Base-T Ethernet port and can be Open Compute Project connected directly to the rack switch.
  • Page 2: Electrical Specifications

    1OU OCP Power Management Controller (PMC) ELECTRICAL SPECIFICATIONS System on Module (SOM) Core All Artesyn current generation shelf and power management controllers utilize a shared SOM that fits onto a customer carrier. The SOM provides the core processing functionality along with storage. Communications from the SOM are routed by the carrier board which provides the mechanical form factor and connections for different shelves.
  • Page 3 1OU OCP Power Management Controller (PMC) ELECTRICAL SPECIFICATIONS 3.3 VDC Output The PMC supports a 3.3 V power output from the edge connector to support the backplane FRU device. This output supports 3.3 V operation at up to 5 mA. PMC Kill PMC Kill is a mate-first, break-last pin to initiate connection to the PSUs through the backplane to safely connect the PMC.
  • Page 4: Pmc Connectors

    1OU OCP Power Management Controller (PMC) PMC CONNECTORS RJ45 Connectors The PMC contains four RJ45 connectors located on the bulkhead of the assembly. The RJ45 location is defined in the mechanical section. Looking from the front, top left RJ45 is #1, top right is #2, bottom left is #3, bottom right is #4. The pinouts of the four connectors are shown below.
  • Page 5 1OU OCP Power Management Controller (PMC) PMC CONNECTORS Pin # Signal Name Description Pin # Signal Name Description ADDR_ID_0 Shelf ID: I2C_CLK_2 PSU #2 PMBus ADDR_ID_1 I2C_SDA_3 PSU #3 PMBus 000 1U power shelf ADDR_ID_2 I2C_CLK_3 PSU #3 PMBus 001 Battery shelf Ground I2C_SDA_4 PSU #4 PMBus...
  • Page 6 The system provides a full Redfish interface aligned with the Redfish 2021.4 version. Where functionality is not available in Redfish OEM extensions may be used. OEM extensions appear under the OEM name Advanced Energy. Redfish is available over HTTP or HTTPS but HTTP can be disabled in the configuration. HTTPS certificates are self-signed.
  • Page 7: Mac Address Information

    1OU OCP Power Management Controller (PMC) PMC SOFTWARE FRU Information The PMC and shelf FRU information is programable via a command line tool. Rack and CDU information can be read/written via Redfish. The command line tool provides direct read access to the EEPROMs. Vout Select (SW Control) The PMC supports a PSU_VOUT_SEL SW command to the collective PSU group for setting PSU Vout between 48 and 51 V (default).
  • Page 8: Mechanical Drawing

    1OU OCP Power Management Controller (PMC) MECHANICAL DRAWING Mechanical Drawing 3D VIEW NOTES: 1. PARTS MUST BE COMPLETELY ASSEMBLED. 2. REFER TO BOM FOR UPDATED PART NUMBERS. 3. QUALITY CONTROLLED DIMENSIONS. THESE DIMENSIONS TO BE INCLUDED IN THE MECHANICAL CPK OF 1.33. 4.
  • Page 9 1OU OCP Power Management Controller (PMC) MECHANICAL DRAWING RJ45 Connector The MPN is TE 2041276-2 or equivalent. The connectors come with spring fingers. They must contact the chassis in order to provide good EMI sealing. The reserved port 2# and 4# should be plugged with a connector cap. Blind Mate The PCB (card edge) of the PMC module plugs into a 2C connector on the chassis side.
  • Page 10 1OU OCP Power Management Controller (PMC) SERVICEABILITY Required Collateral Include (at minimum) schematics, CAD, block diagrams, I2C diagram, switch and jumper settings, service/repair/assembly/disassembly instructions (if applicable), LED definitions. FRU Information FRU labels include part number and serial number. Default Static IP Address The default static IP address should be included on the label.
  • Page 11: Environmental Specifications

    1OU OCP Power Management Controller (PMC) ENVIRONMENTAL SPECIFICATIONS Thermals Thermal specification should exactly match OCP spec (PMI and PMC) - current version v67 section 9. Environmental Operational: • Cold aisle (inlet) temperature: -5ºC to 45ºC • Relative humidity: 10% to 90%, non-condensing •...
  • Page 12 Specifications are subject to change without notice. Not responsible powersales@aei.com (Sales Support) for errors or omissions. ©2023 Advanced Energy Industries, Inc. All rights productsupport.ep@aei.com (Technical Support) reserved. Advanced Energy®, AE® and Artesyn™ are U.S. trademarks +1 888 412 7832 of Advanced Energy Industries, Inc.

Table of Contents