6. Multi I/O modules
Fault
Description
number
Fault short circuit/overload
2 (con
tinuation)
Short circuit/overload at an output
The reaction depends on the
parametrizing Reaction after short
circuit/overload at outputs (SCO)":
Setting V
off" (default):
The output is switched off
Setting V
The output current is limited to
approx. 250 mA.
5
Fault in load voltage for outputs
Load voltage for outputs (V
missing or too low.
1)
Tolerance range of the load voltage supply V
Tab. 6/14: Error messages of the multi I/O modules part 2
Festo P.BE−CPX−EA−EN en 05602d
remains switched
OUT
switch on agai":
OUT
)
OUT
1)
OUT
Please note
Please note when using the multi I/O modules:
If there is a short circuit, all sensor supplies will be
switched off together.
If not parametrized otherwise, the sensor supply voltage
will be switched on again automatically when the short
circuit is eliminated.
Fault treatment
1. Check actuators, eliminate short circuit/over
load (number of faulty channel: see module
diagnostic data).
2. Depending on the parametrizing Reaction
after short circuit/overload at outputs (SCO)":
Set output to 0, then set to 1 again or
·
modify parameter Reaction after short
circuit/overload at outputs (SCO)" to V
switch on again".
If the output current is lower than 400 mA:
·
The voltage will be switched on again
automatically when the short circuit is
eliminated. If the output current is greater
than 400 mA:
Set output to 0, then set to 1 again.
Check the load voltage
·
see Technical specifications" in the appendix.
OUT
6−17