Network Variable Description - Danfoss VLT FC 100 Manual

Hide thumbs Also See for VLT FC 100:
Table of Contents

Advertisement

5. Configuration of the system

5.2. Network Variable Description

5.2.1. - FC VSD Profile - input
Start/Stop
Variable
name:
nviStartStop
5
This variable sends a Start or Stop command to the frequency converter and a reference (0 - 100
%)
Control Word
Variable
name:
nviControlword
The input network variable nviControlWord is a 16-bit word providing additional operational con-
trol of the frequency converter.
For more information about the Control word, please refer to the
tion.
Reset fault
Variable
name:
nviResetFault
This variable sends a reset command to the frequency converter via bit 7 in the Control Word
(0x04BC), see the
22
SNVT
State:
type:
SNVT_switch
0 (False)
1 (True)
1 (True)
1 (True)
0xFF (default)
SNVT
type:
SNVT_state
NB!
N.B.
Please note in the representation of the Control Word in the LonMaker Browser, the
LSB is to the far left.
SNVT
State:
type:
SNVT_switch
0 (False)
1 (True)
0xFF (default)
Danfoss FC Control Profile
MG.11.E1.02 - VLT
Value:
Any
0
1-200
201-255
Any
Boolean 1 bit x 16
Danfoss FC Control Profile
Value:
Any
Any
AUTO (invalid, no ac-
Any
tion)
section.
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Command:
Stop (0x043C)
Running 0%
(0x047C)
Running 0.5 to
100.0%
Running100%
AUTO (invalid,
no action)
State:
sec-
Command:
No reset
Reset (0x04B)