8. Parameters
[2]
[3]
[4]
[5]
[6]
8-03 Control Timeout Time
Range:
8
*
0 s
8-04 Control Timeout Function
Option:
[0]
[1]
[2]
[3]
[4]
[5]
[7]
[8]
[9]
[10]
[20]
54
FC USB
Option A
Option B
Option C0
Option C1
[0.1 - 18000 s]
*
Off
Freeze output
Stop
Jogging
Max. Speed
Stop and trip
Select set-up 1
Select set-up 2
Select set-up 3
Select set-up 4
N2 Override Release
MG.11.E1.02 - VLT
Select the source of the control word: one of two serial interfa-
ces or four installed options. During initial power-up, the fre-
quency converter automatically sets this parameter to
A
[3] if it detects a valid fieldbus option installed in slot A. If the
option is removed, the frequency converter detects a change in
the configuration, sets par. 8-02 back to default setting
Port
, and the frequency converter then trips. If an option is in-
stalled after initial power-up, the setting of par. 8-02 will not
change but the frequency converter will trip and display: Alarm
Option Changed
67
.
This parameter cannot be adjusted while the motor is running.
Function:
Enter the maximum time expected to pass between the recep-
tion of two consecutive telegrams. If this time is exceeded, it
indicates that the serial communication has stopped. The func-
Control Time-out Function
tion selected in par. 8-04
carried out.
In LonWorks the following variables will trigger the Control
Word Time parameter:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
Function:
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks