5. Configuration of the system
Network timer functions monitor node presence and control behaviour in the event of network
problems occurring.
5.8. Network Timer Functions
5.8.1. Control Word Time-out Function
Parameter 8-03 Control Word Timeout Time and parameter 8-04 Control Word Timeout Function
provide a means for the frequency converter to control communication to a controller node.
If a valid control word has not been received within the time specified in par. 8-03, the action
specified in par. 8-04 will be performed. The default action is OFF (no action).
The range of par. 8-03 is: 0.1 to 18,000 seconds (or 5 hours).
5
An update of the control word is triggered by the following SNVT's:
• nviStartStop
• nviResetFault
• nviControlword
• nviDrvSpeedStpt
• nviRefPcnt
• nviRefHz
• nviFeedback 1,2,3
• nviSetPoint 1,2,3
5.8.2. Min. Send Time (Inhibit Timer)
Variable
name:
nciMinSendT
Variable used for limiting bus traffic by setting a minimum sending timer (inhibit timer).
Applies for all output variables.
Format: Days Hours:Minutes:Seconds:Milliseconds.
42
SNVT
Default value:
type:
SNVT_elapsed_tm
00:0:0:500
MG.11.E1.02 - VLT
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Min value:
Max value:
0 0:0:0:100
0 0:01:05:535