Download Print this page

Technical Data - Fronius Agilo 360.0-3 TL Operating Instructions Manual

Grid-connected inverter

Advertisement

Available languages

Available languages

Technical data

Fronius Agilo
Input data
360.0-3 TL
MPP voltage range
Max. input voltage
(at 1,000 W/m²/ -10°C in an open circuit)
Max. input current
Max. short circuit current of the solar modules
Output data
Nominal output power (P
Max. output power
(up to 35 °C ambient temperature)
Nominal grid voltage
Grid voltage tolerance
Nominal output current (three-phase)
Nominal frequency
Total harmonic distortion
Power factor cos phi
Max. permitted grid impedance Z
Max. feedback current
Starting current pulse
Max. output fault current per period
General data
Maximum efficiency
Europ. efficiency
Overnight self-consumption
Cooling
Degree of protection
Indoor device
Outdoor device
electronic area
Dimensions l x w x h
Indoor device
Outdoor device
Weight
Indoor device
Outdoor device
Permitted ambient temperature
(at 95% rel. humidity)
EMC device class
Overvoltage category AC / DC
Pollution level
)
nom
3)
at PCC
max
4)
6)
505 - 820 V DC
1000 V DC
730 A
1095 A
360 kVA
360 kVA
3 ~ 330 V
+15 / -20 %
629,8 A
50 / 60 Hz
< 3 %
0,8 - 1 ind./cap.
47 mOhm
98,50 %
98,30 %
168 W
Controlled forced-air ventila-
tion
IP 40
IP 44
IP 55
1150 x 775 x 1970 mm
1150 x 1055 x 2230 mm
615 kg
660 kg
- 20 °C - +50 °C
3 / 2
1)
1)
2)
5)
-
5)
-
-
A
3
77