Fronius Agilo 360.0-3 TL Operating Instructions Manual page 56

Grid-connected inverter

Advertisement

Available languages

Available languages

Data communication and Solar Net
Fronius Solar Net
Fronius Solar Net was developed to make system add-ons flexible and capable of being
and data interface
used in a wide variety of different applications. Fronius Solar Net is a data network that
enables multiple inverters to be linked up using system add-ons.
It is a bus system that uses a ring topology. One cable is sufficient for communication be-
tween one or several inverters that are connected on the Fronius Solar Net using a sys-
tem add-on.
Fronius Solar Net automatically recognises a wide variety of system add-ons.
In order to distinguish between several identical system add-ons, each one must be as-
signed a unique number.
Similarly, every inverter on the Fronius Solar Net must be assigned a unique number.
Refer to the section entitled 'The Setup menu' for instructions on how to assign a unique
number.
More detailed information on the individual system add-ons can be found in the relevant
operating instructions or on the internet at http://www.fronius.com.
More detailed information on cabling DATCOM components can be found at:
Description of the
The 'Solar Net' LED is on:
'Fronius Solar
the power supply for data communication within the Fronius Solar Net / interface protocol
Net' LED
is OK
The 'Solar Net' LED flashes briefly every 5 seconds:
data communication error in the Fronius Solar Net
-
-
After cutting out because of overcurrent or undervoltage, the inverter attempts to restore
the power supply in the Fronius Solar Net every 5 seconds while the fault is still present.
Once the fault is rectified, power to the Fronius Solar Net will be restored within 5 seconds.
54
 http://www.fronius.com/QR-link/4204101938
Overcurrent (current flow > 3 A, e.g. resulting from a short circuit in the Fronius Solar
Net ring)
Undervoltage (not a short circuit, voltage in Fronius Solar Net < 6.5 V, e.g. if there are
too many DATCOM components on the Fronius Solar Net and not enough electrical
power is available)
In this case, power for the DATCOM components must be supplied by connecting an
additional power supply to one of the DATCOM components.
To detect the presence of an undervoltage, check some of the other DATCOM com-
ponents for faults as required.