Fronius Symo 3.0-3-S Operating Instructions Manual

Fronius Symo 3.0-3-S Operating Instructions Manual

Grid-connected inverter
Hide thumbs Also See for Symo 3.0-3-S:
Table of Contents

Advertisement

/ Perfect Charging / Perfect Welding /
Fronius Symo
3.0-3-S / 3.7-3-S / 4.5-3-S
3.0-3-M / 3.7-3-M / 4.5-3-M
5.0-3-M / 6.0-3-M / 7.0-3-M
8.2-3-M
10.0-3-M / 12.5-3-M / 15.0-3-M
17.5-3-M / 20.0-3-M
Fronius Eco
25.0-3-S / 27.0-3-S
42,0410,2028
Solar Energy
018-08082017
Operating Instructions
Grid-connected inverter
Istruzioni per l'uso
Inverter per impianti fotovoltaici col-
legati alla rete
Manual de instruções
Retificador alternado acoplado à
rede

Advertisement

Table of Contents
loading

Summary of Contents for Fronius Symo 3.0-3-S

  • Page 1 / Perfect Charging / Perfect Welding / Solar Energy Operating Instructions Fronius Symo 3.0-3-S / 3.7-3-S / 4.5-3-S Grid-connected inverter 3.0-3-M / 3.7-3-M / 4.5-3-M Istruzioni per l'uso 5.0-3-M / 6.0-3-M / 7.0-3-M 8.2-3-M Inverter per impianti fotovoltaici col- legati alla rete 10.0-3-M / 12.5-3-M / 15.0-3-M...
  • Page 3 Thank you for the trust you have placed in our company and congratulations on buying this high-quality Fronius product. These instructions will help you familiarise yourself with the product. Reading the instructions carefully will enable you to learn about the many different features it has to offer.
  • Page 5: Table Of Contents

    Explanation of the multifunction current interface ................. Fronius Datamanager 2.0 .......................... Controls, connections and displays on the Fronius Datamanager............Fronius Datamanager during the night or when the available DC voltage is insufficient ...... Using for the first time ........................... Further information on Fronius Datamanager 2.0.................
  • Page 6 Class 10 - 12 status codes........................Customer service ..........................Operation in dusty environments ......................Technical data............................Fronius Symo dummy ........................... Explanation of footnotes ........................Applicable standards and guidelines ....................Warranty terms and conditions, and disposal .................... Fronius manufacturer's warranty ......................
  • Page 7: Safety Rules

    Safety rules General The device is manufactured using state-of-the-art technology and according to recognised safety standards. If used incorrectly or misused, however, it can cause: injury or death to the operator or a third party, damage to the device and other material assets belonging to the operator, inefficient operation of the device.
  • Page 8: Qualified Service Engineers

    Qualified service The servicing information contained in these Operating Instructions is intend- engineers ed only for the use of qualified service engineers. An electric shock can be fa- tal. Do not perform any actions other than those described in the documentation.
  • Page 9: Copyright

    Copyright Copyright of these operating instructions remains with the manufacturer. The text and illustrations are all technically correct at the time of printing. We reserve the right to make changes. The contents of the operating instructions shall not provide the basis for any claims whatsoever on the part of the pur- chaser.
  • Page 10: General

    (e.g. if it is installed in a switch cabinet without suitable heat dissipation). The Fronius Eco does not have an internal boost converter. This results in certain restric- tions in the choice of solar module and string. The minimum DC input voltage (U DC min depends on the grid voltage.
  • Page 11: Proper Use

    Fronius the installation of parts that are not distributed or expressly approved by Fronius. Fronius shall not be liable for any damage resulting from such action. No warranty claims will be entertained.
  • Page 12: Controlling The Inverter Via Demand Response Modes (Drm)

    Response Installation is described in the installation instructions for the Fronius DRM interface. The Modes (DRM) installation instructions for the Fronius DRM interface are available at the following link on the Fronius homepage: http://www.fronius.com/QR-link/4204102292 Example: Device rating plate of a dummy device...
  • Page 13: Criteria For Selecting The Right String Fuses

    String fuses are used in the Fronius Eco to provide additional protection for the solar mod- ules. The maximum short circuit current I , the maximum module return current I or the maxi- mum string fuse rating specified in the module data sheet of the respective solar module is crucial in affording the solar modules the correct fuse protection.
  • Page 14: Data Communication And Solar Net

    Data communication and Solar Net Fronius Solar Net Fronius Solar Net was developed to make system add-ons flexible to use in a variety of and data interface different applications. Fronius Solar Net is a data network that enables multiple inverters to be linked up using system add-ons.
  • Page 15: Description Of The 'Fronius Solar Net' Led

    Overcurrent (current flow > 3 A, e.g. resulting from a short circuit in the Fronius Solar Net ring) Undervoltage (not a short circuit, voltage in Fronius Solar Net < 6.5 V, e.g. if there are too many DATCOM components on the Fronius Solar Net and not enough electrical...
  • Page 16: Example

    After cutting out because of overcurrent or undervoltage, the inverter attempts to restore the power supply in the Fronius Solar Net every 5 seconds while the fault is still present. Once the fault is rectified, power to the Fronius Solar Net will be restored within 5 seconds.
  • Page 17 This S0 meter can be positioned directly at the feed-in point or in the consumption branch. As one of the settings on the Fronius Datamanager website, a dynamic power re- duction can be set under the "EVU Editor" menu subitem (see Fronius Datamanager Op- erating Instructions under www.fronius.com/QR-link/4204260173DE)
  • Page 18: Fronius Datamanager 2.0

    Switch position A Default IP address with opening of the WLAN access point Fronius Datamanager 2.0 uses the set IP address 169.254.0.180 to establish a direct connection to a PC via LAN. Setting the IP switch to position A also opens an access point to enable a direct WLAN connection to the Fronius Datamanager 2.0.
  • Page 19 WLAN LED Flashing green: Fronius Datamanager 2.0 is in Service mode (IP switch on the Fronius Datamanager 2.0 plug-in card is in position A or Ser- vice mode has been activated via the inverter display, the WLAN access point is open)
  • Page 20: Fronius Datamanager During The Night Or When The Available Dc Voltage Is Insufficient

    The Night Mode parameter under "Display Settings" in the Setup menu is preset to OFF in ager during the the factory. night or when the For this reason the Fronius Datamanager cannot be accessed during the night or when the available DC volt- available DC voltage is insufficient. age is insufficient To nevertheless activate the Fronius Datamanager, switch the inverter off and on again at the mains and press any key on the inverter display within 90 seconds.
  • Page 21: Using For The First Time

    Connect inverter with Fronius Datamanager 2.0 or Fronius Datamanager Box 2.0 to the Fronius Solar Net When networking several inverters together in Fronius Solar Net: Set the Fronius Solar Net master / slave switch on the Fronius Datamanager 2.0 plug- in card correctly One inverter with Fronius Datamanager 2.0 = master All other inverters with Fronius Datamanager 2.0 = slave (the LEDs on the Fronius...
  • Page 22 If the technician wizard is not run, no specifications regarding power reduction are set. Running the Solar Web wizard is mandatory. Run the Solar Web wizard and follow the instructions. The Fronius Solar.web homepage is displayed, the Fronius Datamanager 2.0 web page is displayed.
  • Page 23: Further Information On Fronius Datamanager 2.0

    Where necessary, run the technician wizard and follow the instructions Further informa- Further information on the Fronius Datamanager 2.0 and other start-up options can be tion on Fronius found at: Datamanager 2.0  http://www.fronius.com/QR-link/4204260191EA...
  • Page 24: Controls And Indicators

    Controls and indicators Controls and indi- cators (5) (6) (7) (8) Item Description Display for displaying values, settings and menus Monitoring and status LEDs General status LED on steady, if a status code is being displayed on the monitor (red for error, orange for warning) if the process of feeding energy into the grid is interrupted while error handling (the inverter waits for an acknowledgement or for an...
  • Page 25: Display

    Display areas in Display mode Display Power for the display comes from the mains voltage. Depending on the setting selected in the Setup menu, the display can be kept on all day. IMPORTANT! The display on the inverter is not a calibrated measuring device. A slight in- accuracy in comparison with the energy meter used by the power supply company is in- Display areas in Setup mode trinsic to the system.
  • Page 26: Navigation At The Menu Level

    Navigation at the menu level Activate display Press any key backlighting The display backlighting is activated. There is an option under 'Display Settings' in the SETUP menu to set the display back- lighting so that it is on all the time or off all the time. Automatic deacti- If no key is pressed for 2 minutes, vation of display...
  • Page 27: Values Displayed In The Log Menu Item

    Fronius Eco: The total current from both measuring channels is displayed. Both channels are shown separately in SolarWeb. Time date - Time and date on the inverter or in the Fronius Solar Net ring Values displayed Energy fed in (kWh / MWh)
  • Page 28: Setup Menu Item

    SETUP menu item Initial setting The inverter is pre-configured and ready to use. There is no need to enter any initial set- tings before using it to feed energy into the grid, as this is a fully-automated process. The SETUP menu item allows the initial settings of the inverter to be changed easily to bring it in line, as closely as possible, with the preferences and requirements of the user.
  • Page 29: Setting Entries On The Setup Menu, General

    If no key is pressed for 2 minutes, The inverter switches from wherever it is on the menu level back to the 'NOW' display mode (exception: 'Standby' Setup menu entry), the display backlighting goes out. the amount of energy currently being fed in is displayed. Setting entries on Entering the SETUP menu item the Setup menu,...
  • Page 30 An overview of the values that can be changed is displayed. Use the 'Up' or 'Down' keys to select 'Set time' Press the 'Enter' key The current time appears. (HH:MM:SS, 24-hour clock), the 'tens' digit for the hour will flash. Use the 'Up' and 'Down' keys to select a value for the 'tens' digit for the hour Press the 'Enter' key...
  • Page 31: Menu Items In The Set-Up Menu

    Setting range Status / inverter number / protocol type Status Indicates data communication is taking place via Fronius Solar Net or that a data commu- nications error has occurred Inverter number Sets the number (= address) of the inverter in a system with several solar inverters...
  • Page 32: Usb

    Procedure: Download the relevant update file 'froxxxxx.upd' (e.g. from http://www.fronius.com; xxxxx stands for the version number) NOTE! To successfully update the inverter software, the USB stick provided for the purpose must not have a hidden partition or any encryption (see chapter "Suit- able USB sticks").
  • Page 33: Relays

    Logging interval Activate / deactivate the logging function and specify a logging interval Unit Minutes Setting range 30 min. / 20 min./ 15 min./ 10 min./ 5 min./ No log Factory setting 30 min. 30 min. The logging interval is 30 minutes; every 30 minutes new log- ging data will be saved on the USB stick.
  • Page 34: Energy-Manager(In Relay Menu Item)

    Relay test Function test to determine whether the floating switch contact switches Switch-on point (only if 'Energy Manager' function is activated) for setting the effective power limit beyond which the floating switch contact is switched on Factory setting 1000 W Setting range Switch-off point - max.
  • Page 35: Time / Date

    Activate/deactivate automatic changeover between summer and winter time IMPORTANT! Only use the automatic summer/winter time changeover function if the Fronius Solar Net ring does not include any LAN- or WLAN-compatible system compo- nents (e.g. Fronius Datalogger Web, Fronius Datamanager or Fronius Hybridmanager).
  • Page 36: Energy Yield

    DATCOM will not run at night, the inverter will not need any AC current in order to supply power to the Fronius Solar Net. The display is switched off during the night and the Fronius Datamanager is not available. Contrast...
  • Page 37: Fan

    Feed-in tariff Set the remuneration rate for energy fed into the grid Setting range 2 digits, 3 decimal places Factory setting (depends on country setup) To check that the fan is working correctly Setting range Test fan #1 / Test fan #2 (depending on the device) Use the 'Up' and 'Down' keys to select the desired fan Testing of the selected fan is initiated by clicking 'Enter'.
  • Page 38: The Info Menu Item

    Insulation resistance of the PV system U PV 1 / U PV 2 (U PV 2 is not available on the Fronius Symo 15.0-3 208) Current DC voltage on the terminals, even if the inverter is feeding no power into the grid...
  • Page 39: Version

    GVDPRv - reduction gradient used to reduce the power, e.g. 10% per volt above the GVDPRe threshold. Message - activates the sending of an info message via Fronius Solar Net Fault Ride Through: Status – Default setting: OFF...
  • Page 40: Switching The Key Lock On And Off

    Switching the key lock on and off General The inverter has a key lock function. When the key lock is active, the Setup menu is not accessible, i.e. the setup data cannot be changed accidentally (or maliciously). The code 12321 has to be entered in order to activate / deactivate the key lock. Switching the key Press the 'Menu' key lock on and off...
  • Page 41: Usb Stick As A Data Logger And For Updating Inverter Software

    At any time, the logging data stored on the USB flash drive can be imported into the Fronius Solar.access software using the FLD file that was logged at the same time, viewed directly in third-party programs (e.g. Microsoft® Excel) using the CSV file logged at the same time.
  • Page 42: Usb Flash Drive For Updating The Inverter Software

    USB symbol on the inverter display, e.g. in display mode 'NOW': If the inverter detects a USB flash drive, the USB symbol will appear in the top right corner of the display. When inserting a USB flash drive, check whether the USB symbol is displayed (it may also flash).
  • Page 43: The Basic Menu

    The Basic menu is used to set the following parameters, which are important for installing sic menu and operating the inverter: MPP Tracker 1 / MPP Tracker 2 MPP Tracker 2: ON / OFF (MultiMPP Tracker devices only, excluding Fronius Symo 15.0-3 208)
  • Page 44: Settings If The "Dc Spd" Option Is Installed

    DC operating mode: MPP AUTO / FIX / MPP USER MPP AUTO: normal operating status; the inverter automatically searches for the ideal operating point FIX: for entering a fixed DC voltage at which the inverter will operate MPP USER: for entering a lower MP voltage above which the inverter will search for its ideal operating point Dynamic Peak Manager: ON / OFF Fixed voltage: for entering the fixed voltage...
  • Page 45: Autotest

    Status diagnostics and troubleshooting Displaying status The inverter performs a system self diagnosis that automatically detects many faults that codes may occur and shows them on the display. This means you are promptly made aware of malfunctions in the inverter and the photovoltaic system, or of any installation or operating faults.
  • Page 46: Hinweise Zum Autotest

    Fan 1 error Fan 2 error *) If the status code is displayed all the time: notify a Fronius-trained service engineer **) Fault is rectified automatically. If this status code keeps recurring, contact your system engineer Status codes –...
  • Page 47 Code Description Behaviour Remedy Fixed voltage mode has been selected instead of MPP voltage mode, and the fixed voltage has been set to too low or too high a value. Safety cut-out via option card or RECER- The inverter is not feeding BO has triggered any energy into the grid.
  • Page 48 (five 479 status codes in any energy into the grid. a row) *) If the status code is displayed all the time: Notify a Fronius-trained service technician **) If this status code keeps recurring, contact your system engineer.
  • Page 49: Status Codes - Class 5

    Status codes – Class 5 status codes do not generally interfere with feeding energy into the grid, but can Class 5 cause restrictions. These status codes are displayed until they are acknowledged by pressing a key (however, the inverter continues to operate normally in the background). Code Description Behaviour...
  • Page 50: Class 6 Status Codes

    *) If the status code is displayed all the time: Notify a Fronius-trained service technician. **) If this status code keeps recurring, contact your system engineer. Class 6 status Some of the class 6 status codes necessitate intervention by a Fronius-trained service en- codes gineer.
  • Page 51: Status Codes - Class 7

    *) If the status code is displayed all the time: notify a Fronius-trained service engineer **) Fault is rectified automatically. If this status code keeps recurring, contact your system engineer Status codes – Class 7 status codes relate to the control system, the configuration and inverter data re- Class 7 cording, and may directly or indirectly affect the process of feeding energy into the grid.
  • Page 52: Class 10 - 12 Status Codes

    Warning message on the internal processor status display *) If the status code is displayed all the time: Notify a Fronius-trained service technician Class 10 - 12 sta- 1000 - 1299- Provide information on the status of the internal processor program...
  • Page 53: Customer Service

    Customer service IMPORTANT! Contact your Fronius dealer or a Fronius-trained service technician if an error appears frequently or all the time an error appears that is not listed in the tables Operation in When operating the inverter in extremely dusty environments:...
  • Page 54: Technical Data

    Technical data Fronius Symo 3.0-3-S 3.7-3-S 4.5-3-S Input data MPP voltage range 200 - 800 V DC 250 - 800 V DC 300 - 800 V DC Max. input voltage 1000 V DC (at 1,000 W/m² / -10 °C in an open circuit) Min.
  • Page 55 Fronius Symo 3.0-3-M 3.7-3-M 4.5-3-M Input data MPP voltage range 150 - 800 V DC 150 - 800 V DC 150 - 800 V DC Max. input voltage 1000 V DC (at 1,000 W/m² / -10 °C in an open circuit) Min.
  • Page 56 Fronius Symo 5.0-3-M 6.0-3-M 7.0-3-M Input data MPP voltage range 163 - 800 V DC 195 - 800 V DC 228 - 800 V DC Max. input voltage 1000 V DC (at 1,000 W/m² / -10 °C in an open circuit) Min.
  • Page 57 Fronius Symo 8.2-3-M Input data MPP voltage range (PV1 / PV2) 267 - 800 V DC Max. input voltage 1000 V DC (at 1,000 W/m² / -10 °C in an open circuit) Min. input voltage 150 V DC Max. input current (I PV1 / I PV2) 2 x 16.0 A...
  • Page 58 Fronius Symo 10.0-3-M 12.5-3-M Input data MPP voltage range 270 - 800 V DC 320 - 800 V DC Max. input voltage 1000 V DC (at 1,000 W/m² / -10 °C in an open circuit) Min. input voltage 200 V DC Max.
  • Page 59 Fronius Symo 15.0-3-M 17.5-3-M 20.0-3-M Input data MPP voltage range 320 - 800 V DC 370 - 800 V DC 420 - 800 V DC Max. input voltage 1000 V DC (at 1,000 W/m² / -10 °C in an open circuit) Min.
  • Page 60 Fronius Eco 25.0-3-S 27.0-3-S Input data MPP voltage range 580 - 850 V DC 580 - 850 V DC Max. input voltage 1000 V DC (at 1,000 W/m² / -10 °C in an open circuit) Min. input voltage 580 V DC Max.
  • Page 61: Fronius Symo Dummy

    Fronius Symo Input data Dummy 3 - 10 kW Dummy 10 - 20 kW dummy Nominal grid voltage 1 ~ NPE 230 V Grid voltage tolerance +10 / -5 % Nominal frequency 50 - 60 Hz General data Degree of protection...
  • Page 62: Warranty Terms And Conditions, And Disposal

    To obtain the full warranty period for your newly installed Fronius inverter or storage sys- tem, please register at: www.solarweb.com. Disposal If you decide in the future to replace your inverter, Fronius will take back the old device and arrange for it to be recycled in an appropriate manner.

Table of Contents