Download Print this page

Fronius Agilo 360.0-3 TL Operating Instructions Manual page 75

Grid-connected inverter

Advertisement

Available languages

Available languages

Class 4 status
Some of the class 4 status codes necessitate intervention by a Fronius-trained service en-
codes
gineer.
Code
Description
No communication with power
401
stage set possible
Power stage set temperature
406
sensor faulty
Internal temperature sensor
407
faulty
Fixed voltage mode has been
selected instead of MPP volt-
412
age mode, and the fixed volt-
age has been set to too low or
too high a value.
External Emergency Stop line
415
is blocked
No communication possible
416
between power stage set and
control system.
No communication possible
425
with the power stage set
Intermediate circuit charging
426
takes too long
Power stage set not ready for
427
too long (timeout)
Bootloading process interrupt-
431
ed
Receiving incorrect fault infor-
436
mation from the power stage
set
General error handling started
437
in the power stage set
Receiving incorrect fault infor-
438
mation from the power stage
set
-
Compatibility error (e.g.
due to replacement of a
445
PC board)
-
Invalid power stage set
configuration
457
Grid relay sticking
Error when recording the
459
measuring signal for the insu-
lation test
Reference voltage source for
the digital signal processor
460
(DSP) is working out of toler-
ance
Behaviour
The inverter will automatically
attempt to connect again and,
if possible, will resume feeding
energy into the grid
-
The inverter is not feeding any
energy into the grid.
The inverter will automatically
attempt to connect again and,
if possible, will resume feeding
energy into the grid
Short-term interruption while
feeding energy into the grid
The inverter resumes with its
startup routine.
The inverter is in bootloading
mode and is not feeding any
energy into the grid
Short-term interruption while
feeding energy into the grid
The inverter resumes with its
startup routine.
The inverter is not feeding any
energy into the grid for safety
reasons.
The inverter is not feeding any
energy into the grid.
Remedy
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
If this status code keeps recur-
ring, contact your system engi-
neer
Fault is rectified automatically;
If this status code keeps recur-
ring: notify a Fronius-trained
service engineer
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
Fault is rectified automatically
If this status code keeps recur-
ring, contact your system engi-
neer
Repeat the update process
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
Fault is rectified automatically
If this status code keeps recur-
ring, contact your system engi-
neer
Update the inverter firmware;
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
Notify a Fronius-trained ser-
vice engineer
73

Advertisement

loading

This manual is also suitable for: