Si33-102.book Page 65 Tuesday, June 26, 2001 3:18 PM
SiE33-102
4.4
Setting Modes
There are the following three setting modes.
Setting mode 1 (H1P off)
Used to select the cool/heat setting, low-noise run and sequential start.
Setting mode 2 (H1P on)
Used to modify the running status and to program addresses, etc. Usually used in servicing the system.
Monitor mode (H1P flashing)
Used to check the programs made in the setting mode 2, the number of units being connected, and other
entries.
Functions of Pushbutton Switches
Used to set the cool/heat select.
IN/D
OUT/D
C / H
UNIT
UNIT
SELECT
SS1
C / H select
MODE TEST
IND
MAIN
SUB
H1P H2P
H3P
H4P
H5P
MODE
SET
RETURN
WIRING CHECK
RESET
BS1
BS2
BS3
BS4
Mode Change
Using the MODE button, the modes can be changed as follows.
Press the MODE
button once.
Monitor mode
MODE
Flashing
H1P
General Information
L.N.
SEQ.
O.P
START
Used to rearrange the addresses in modifying the
H6P
H7P
cabling or increasing the number of indoor units.
Used to check for wrong cabling.
BS5
Used for field programming.
Used to change the setting modes.
Hold down the MODE
(Normal)
button for 5 seconds.
Setting mode 1
Press the MODE
MODE
button once.
Off
H1P
: http://splitoff.ru/tehn-doc.html
Test Operation
(V1549)
Setting mode 2
MODE
On
H1P
(V1328)
65