Nomenclature Nomenclature Indoor FL(Y) 15 E X V1 Power Supply V1: 1 phase 50 Hz 220-240V Production X: OYLM Product Series C: C Series E: E Series Capacity 15: 15000 Btu/hr Model Ceiling Convertible (Cooling Only) FH: Ceiling Exposed (Cooling Only) FLY: Ceiling Convertible (Heatpump) FHY: Ceiling Exposed (Heatpump) Outdoor...
Application Information Application Information Operating Range Ensure the operating temperature is in allowance range. Cooling Outdoor DB (°C) The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. Indoor WB (°C) Heating Outdoor WB (°C)
Application Information Installation Guideline Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them. Installation Diagram Indoor Unit Air Discharge Louver Signal Receiver Indicator Lights Air Intake Grille Air Filters (Inside Air Intake Grille) Refrigerant piping Air Intake Air Intake Air Intake Nozzle...
Application Information Cable Size FL15EXV1 FL20EXV1 FL25EXV1 FL28EXV1 FL28EXV1 Model Unit R15CXV1 R20CXV1 R25CXV1 R28CXV1 R30DXV1 Power supply cable size Number of wire Interconnection cable size Number of wire Recommended fuse FL35EXV1 FL40EXV1 FL50EXV1 FH62CXV1 Model Unit R35DXV1 R40DXV1 R40DXY1...
The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 7.6m, then additional charge after vacuuming is not necessary. If the piping length is more than 7.6m, then use the additional charge (g) per additional 1m length as tabulated: R22 – Cooling Only Indoor FL15EXV1 FL20EXV1 FL25EXV1 FL28EXV1 FL35EXV1 FL40EXV1 FL50EXV1 FH62CXV1...
Sound Data Sound Data Sound Pressure Level 1/1 Octave Sound Pressure (dB, ref 20μPa) Overall Noise Model Speed (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FL(Y)15EXV1 High FL(Y)20EXV1 High FL(Y)25EXV1 High FL(Y)28EXV1 High FL(Y)35EXV1 High FL(Y)40EXV1 High FL(Y)50EXV1 High FH(Y)62CXV1...
Engineering & Physical Data Engineering & Physical Data Engineering Data – R22 MODEL INDOOR UNIT FL15EXV1 FL20EXV1 FL25EXV1 MODEL OUTDOOR UNIT R15CXV1 R20CXV1 R25CXV1 Btu/h 12000 19000 24000 NOMINAL COOLING CAPACITY 3520 5570 7030 NOMINAL TOTAL INPUT POWER (COOLING) 1288...
Engineering & Physical Data Engineering Data - R22 MODEL INDOOR UNIT FL40EXV1 FL50EXV1 FH62CXV1 MODEL OUTDOOR UNIT R40DXY1 R50DXY1 R61DXY1 Btu/h 38000 47500 56000 NOMINAL COOLING CAPACITY 11140 13900 16410 NOMINAL TOTAL INPUT POWER (COOLING) 3800 5050 5593 NOMINAL RUNNING CURRENT (COOLING) 6.23 8.48 9.40...
Engineering & Physical Data Safety Device INDOOR FL(Y)15EXV1 FL(Y)20EXV1 MODEL OUTDOOR R(Y)15CXV1 RY18CXV1 R(Y)20CXV1 TYPE HIGH PRESSURE OPEN kPa / psi SWITCH CLOSE kPa / psi TYPE SAFETY LOW PRESSURE DEVICE OPEN kPa / psi SWITCH CLOSE kPa / psi PHASE SEQUENCER DISC.
Engineering & Physical Data INDOOR FLY35EXV1 FLY40EXV1 FLY40EXV1 MODEL OUTDOOR RY35DXV1 RY40DXV1 RY40DXY1 TYPE HIGH PRESSURE OPEN kPa / psi 2937 / 426 SWITCH CLOSE kPa / psi 2413 / 350 TYPE SAFETY LOW PRESSURE DEVICE OPEN kPa / psi SWITCH CLOSE kPa / psi...
16°C WB. 25°C is located between 24°C & 27°C Example: for 19°C WB. Model: FL15EXV1 – R15CXV1 Thus, Interpolation needs to be applied. Indoor Condition: 25°C DB, 17°C WB 2. Refer to the Indoor WB column, Outdoor Condition: 37°C DB 17°C is located between 16°C &...
Page 28
Performance Data (b) Indoor Condition: 25°C DB, 16°C WB By Interpolation Method Outdoor Condition: 35°C DB 25°C – 24°C – 3.51kW ⇒ Outdoor temperature 27°C – 24°C 3.52kW – 3.51kW 35°C ⇒ x = 3.51kW Similarly, = 2.71kW 3.51 2.57 1.29 = 1.29kW 3.52...
Outlines & Dimensions Model: R(Y)30/40DXV1 / R(Y)40/50/61DXY1 MADE IN MALAYSIA Dimension Model R(Y)30/40DXV1 / 1030 826 400 410 746 142 R(Y)40/50/61DXY1 Note: Dimension in mm...
Wiring Diagrams Wiring Diagrams Cooling Only Indoor Unit Outdoor Unit Model: FL15EXV1 Model: R15CXV1 INDOOR COIL SENSOR ROOM RETURN AIR SENSOR TRANSFORMER WIRED OR WIRELESS REMOTE CONTROLLER HIGH IONIZER BLACK BLACK YELLOW YELLOW BROWN BROWN ORANGE ORANGE KEY: - FIELD SUPPLY WIRING...
Wiring Diagrams Indoor Unit Outdoor Unit Model: FL20/25EXV1 Model: R20/25CXV1 INDOOR COIL SENSOR ROOM RETURN AIR SENSOR TRANSFORMER WIRED OR WIRELESS REMOTE CONTROLLER HIGH IONIZER BLACK BLACK YELLOW YELLOW BROWN BROWN ORANGE ORANGE KEY: - FIELD SUPPLY WIRING BLACK AS: AIR SWING MOTOR COMP.
Wiring Diagrams Indoor Unit Outdoor Unit Model: FL28EXV1 Model: R28CXV1 INDOOR COIL SENSOR ROOM RETURN AIR SENSOR TRANSFORMER WIRED OR WIRELESS REMOTE CONTROLLER HIGH IONIZER BLACK BLACK YELLOW YELLOW BROWN BROWN ORANGE ORANGE KEY: - FIELD SUPPLY WIRING BLACK AS: AIR SWING MOTOR COMP.
Wiring Diagrams Indoor Unit Outdoor Unit Model: FL28EXV1 Model: R30DXV1 INDOOR COIL SENSOR ROOM RETURN AIR SENSOR TRANSFORMER WIRED OR WIRELESS REMOTE CONTROLLER HIGH IONIZER BLACK BLACK YELLOW YELLOW BROWN BROWN ORANGE ORANGE KEY: - FIELD SUPPLY WIRING BLACK AS: AIR SWING MOTOR COMP.
Service & Maintenance Service & Maintenance • Disconnect from main supply before servicing the air conditioner. • The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention. Components Maintenance Procedures Period...
Page 73
Service & Maintenance Pre start up maintenance (After extended shutdown) Inspect thoroughly and clean indoor and outdoor units. Clean or replace air fi lters. Clean condensate drain line. Clean clogged indoor and outdoor coils. Check fan imbalance before operation. Tighten all wiring connections and panels. Check for refrigerant leakage.
Troubleshooting Troubleshooting Indicator Lights LED Indicator Light Display - Cooling Only LED Indicator Light Display - Heatpump POWER TIMER SLEEP POWER TIMER HEAT / SLEEP LED Light Diagnostic Table Error Operation / Action Code Faulty Indication GREEN ORANGE Cooling mode Timer On Sleep mode On Heating mode...
Page 75
Troubleshooting Phase Sequencer The unit with Scroll Compressor only can rotate in one direction. For this reason, a protective device (phase sequencer) is fi tted to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase sequencer operates, and the unit will not start. This device is located in the control box of the outdoor unit.
Page 76
Troubleshooting Error Code / Fault Condition When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer.
Page 77
Troubleshooting Diagnostic Guidelines By means of pressure readings: Data Pressure Probable cause Circuit High side • 1. Overcharged with refrigerant. Low side • 2. Non-condensable gases in refrigerant circuit (e.g. air). 3. Obstructed air-intake / discharge. 4. Hot air short circuiting in outdoor unit. •...