Detailed Explanation Of Setting Modes - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

Field Setting for SkyAir Indoor Unit
4.5

Detailed Explanation of Setting Modes

4.5.1 Air Flow Direction Setting (FFQ)
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to "01."
Setting Table
4.5.2 Filter Sign Setting (FFQ & FHQ)
If switching the filter sign ON time, set as given in the table below.
Set Time
Setting
Contamination Light
Contamination Heavy
4.5.3 Range of Air Flow Direction Setting (FFQ)
Make the following air flow direction setting according to the respective purpose.
4.5.4 Fan Speed OFF When Thermostat is OFF (FFQ & FHQ)
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting
to "Fan OFF."
∗ Used as a countermeasure against odor for barber shops and restaurants.
Setting Table
140
Mode No.
First Code No.
13 (23)
1
Filter Specs.
Mode No.
First Code No.
13 (23)
Mode No.
First Code No.
11(21)
Second Code
No.
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Long Life
01
2,500
02
1,250
Second Code No.
4
01
02
03
Second Code No.
2
SiENBE18-621
Setting
Setting
Upward (Draft prevention)
Standard
Downward (Ceiling soiling
prevention)
Setting
01
02
Fan OFF
Test Operation