Http://Splitoff.ru/Tehn-Doc.html - Daikin VRV System R-22 PLUS Series Manual

Table of Contents

Advertisement

Si33-102.book Page 69 Tuesday, June 26, 2001 3:18 PM
SiE33-102
No Setting item
Description
1
EMG
Emergency operation
(Emergency
when Inverter type
operation 1)
outdoor unit malfunctions.
S
2
Cool/heat
Address for cool/heat
unified
unified operation
address
S
3
Low noise /
Address for low noise
demand
/ demand operation
address
S
4
Forced fan
Indoor unit fan turns
switch
while unit is stopped.
S
Push 3 times
5
Indoor unit
Allows operation of
forced
indoor unit from
operation
outdoor unit
S
Fixes compressor frequency.
6
Frequency fix
INV : (60Hz + OFF)
STD 1 : (ON+OFF)
STD 2 : (ON+OFF)
S
7
TE setting
Low pressure setting
for cooling
S
8
TC setting
High pressure setting
Note 1
for heating
S
Push 3 times
9
Defrost
Temperature setting
setting
for defrost
Note 1
S
10
Air Net
Address for
address
Air Net
S
Initial setting (EMG)
General Information
LED display
LED display
H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
Emergency operation
R
Normal operation
Address
0
Binary number
1
R
(6 digits)
2
31
Address
0
Binary number
1
R
(6 digits)
2
31
Forced fan operation
R
(H tap)
Normal operation
Forced fan operation
(H tap)
R
Normal operation
Frequency fix
R
Normal operation
High
R
Normal (factory set)
Low
R
Quick defrost
R
Normal (factory set)
Slow defrost
Address
0
Binary number
1
R
(6 digits)
2
63

: http://splitoff.ru/tehn-doc.html

Test Operation
LED display
H1P H2P H3P H4P H5P H6P H7P
R
R
S
S
R
R
S
S
S
S
R
R
S
S
S
R
R
S
S
R
R
S
R
R
S
S
R
R
S
S
R
R
S
S
S
R
R
S
S
S
R
RETURN BUTTON
SET BUTTON
S
(V1828)
69

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VRV System R-22 PLUS Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents