Situation
The display on the central remote control does not change from its initial state after turning power ON.
Initial display of the central remote control
Cause
1. None of the indoor units connected to the central remote control have been given a group No.
2. The connector for setting the master control inside the central remote control is disconnected.
Remedial Action
Set a centralized control group No. for each indoor unit with the respective remote controls.
Connect the connector for setting the master control in one of the central remote control.
Main Points
If the setting for master control has been changed, reset the power to the unit at the ON/OFF switch or
the forced reset switch of the control.
Activate power to the central remote control, unified ON/OFF control and indoor unit before setting the
centralized control group No.
For details on how to set the centralized control group number, refer to the installation manual.