Dell EMC ME4084 Owner's Manual page 91

Hide thumbs Also See for ME4084:
Table of Contents

Advertisement

Number
Severity
Description/Recommended actions
273
Info.
PHY fault isolation has been enabled or disabled by a user for the indicated enclosure and controller module.
Recommended actions:
274
Warning
The indicated PHY has been disabled, either automatically or by a user. Drive PHYs are automatically disabled
for empty disk slots or if a problem is detected. The following reasons indicate a likely hardware fault:
Recommended actions:
275
Info.
The indicated PHY has been enabled.
Recommended actions:
276
Info.
A mirror set was created.
Recommended actions:
277
Info.
A mirror set was deleted.
Recommended actions:
278
Info.
A mirror set was verified.
No action is required.
Disabled because of error count interrupts
Disabled because of excessive PHY change counts
PHY is ready but did not pass COMINIT
If none of the preceding reasons apply, no action is required.
If any of the preceding reasons are indicated and the event occurs shortly after the storage system is
powered up, do the following:
Shut down the Storage Controllers. Then turn off the power for the indicated enclosure wait a few
seconds, and turn it back on.
If the problem recurs and the event message identifies a disk slot, replace the disk in that slot.
If the problem recurs and the event message identifies a module, do the following:
If the indicated PHY type is Egress, replace the cable in the module's egress port
If the indicated PHY type is Ingress, replace the cable in the module's ingress port
For other indicated PHY types or if replacing the cable does not fix the problem, replace the
indicated module.
If the problem persists, check for other events that may indicate faulty hardware, such as an event
indicating an over-temperature condition or power supply fault, and follow the recommended actions
for those events.
If the problem persists, the fault may be in the enclosure midplane. Replace the chassis FRU.
If any of the preceding reasons are indicated and this event is logged shortly after a failover, user-initiated
rescan, or restart, do the following:
If the event message identifies a disk slot, reseat the disk in that slot.
If the problem persists after reseating the disk, replace the disk.
If the event message identifies a module, do the following:
If the indicated PHY type is Egress, replace the cable in the module's egress port.
If the indicated PHY type is Ingress, replace the cable in the module's ingress port.
For other indicated PHY types or if replacing the cable does not fix the problem, replace the
indicated module.
If the problem persists, check for other events that may indicate faulty hardware, such as an event
indicating an over-temperature condition or power supply fault, and follow the recommended actions
for those events.
If the problem persists, the fault may be in the enclosure midplane. Replace the chassis FRU.
No action is required.
No action is required.
No action is required.
Events and event messages
91