Channel Diagnostics - Siemens SIMATIC ET 200MP Equipment Manual

Hide thumbs Also See for SIMATIC ET 200MP:
Table of Contents

Advertisement

Interrupts and diagnostic, error, and system alarms
6.3 Alarms
6.3.3

Channel diagnostics

Function
Channel diagnostics provides information about channel faults in modules.
Channel faults are mapped as channel diagnostics in IO diagnostic data records.
The "RDREC" instruction is used to read the data record.
Structure of the diagnostic data records
• The IM 155-5 MF HF interface module maps channel faults by means of extended channel
diagnostics.
The data records supported by the ET 200MP are based on the standard PROFINET IO -
Application Layer Service Definition V2.3.
You can purchase the standards from the PROFIBUS User Organization on the Internet
(http://www.profibus.com).
Codes of the extended channel diagnostics
With the IM 155-5 MF HF interface module, the following extended channel diagnostics are
reported by the interface module in slot 1:
Table 6- 4
Manufacturer-specific diagnostics in the USI
ChannelError-
ExtendedChan-
Type
nel
ErrorType
0x0601
0x0682
0x0602
0x0692
0x0602
0x069A
0x0602
0x069B
0x0602
0x0696
0x0602
0x0697
0x0610
0x06B1
0x0610
0x06B2
0x0602
0x069C
54
Associated value
Diagnostics
(AddValue)
Slot
Communication with slot <No.> has failed
Slot
Permitted number of I/O modules exceeded
Slot
Interface module in incorrect slot
Slot
Permitted number of power supply modules exceeded
0
No U connector detected on an IM port
0
More than one bus master module (IM/CPU) detected
Slot
Power budget error (overload has been detected in at least one
power segment)
0
Error IM power supply: Power supply not active or power supply
active
0x00
Diagnostics with incorrectly plugged BusAdapter
Interface module IM 155-5 MF HF (6ES7155-5MU00-0CN0)
Equipment Manual, 11/2023, A5E53268530-AA