Main Features Of Cs1140 - Siemens AlgoRex CS1140 Planning

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

Main features of CS1140

3
Main features of CS1140
Systems that can be connected
AlgoRex® DS11
Collective
AnalogPLUS
interactive + ex interactive + wireless (radio)
TM
Sinteso
FD20
addressed
Older detector systems
collective detectors
MS6 / MS7 / MS9
Addressable detectors
MS9i / MS9i-PLUS / MS716i
CBA8000/TS9000
12
Building Technologies
Fire Safety & Security Products
Fire detection system that can be configured in a modular manner
2150 detectors possible per CC1143; 980 detectors possible per CC1142; 600
detectors possible per CI1142
For processing collective and addressable detectors
Logical and physical structure totally separate
Control panel module as main CPU (for larger systems)
Operating terminal as main CPU (for smaller to medium-sized systems)
Interfaces for VdS peripheral devices, printer, PSA/pager, host systems, PLC
Different input and output modules
Extinguishing control module that functions autonomously
Special mimic display activation module
Multiple detector logic
Parameterizable detector algorithms for interactive and Sinteso
Central panel electronics can be installed in 4 different housing series
Up to 16 freely selectable station types per C bus
Convenient operation thanks to softkeys and large display
Up to 64 independent logical AREAS (organizational levels)
SINGLE AREA or MULTIPLE AREA operation
Event memory with sub-menu / search functions
Integrated real-time clock with backup battery
Automatic summer/winter time changeover
integrated degraded mode function
Flexible detector parameterization via maintenance PC
Operation
Main CPU B3Q...
CI11
CS1140 control panel pallet
Main CPU
CC11
E3X10x
CPU
WINDOWS-based
configuration software
AlgoWorks
TM
detectors
Operation
CT11
CK11
Gateway
008725_h_en_--
06.2011