Power Supply; Power Supply To Control Panel - Siemens AlgoRex CS1140 Planning

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

35

Power supply

35.1

Power supply to control panel

Battery charging unit contained in E3X10.
Is one of the max. 16 I bus components
CC11
Battery charching
unit
E3X10.
* TF = temperature sensor for battery temperature monitoring
Building Technologies
Fire Safety & Security Products
Concept
The power supply for the CS1140 fire detection system consists of:
Converter
Battery charging unit (integrated in E3X10. or by means of E3C011)
Batteries
Special functions
Automatic battery load test
Battery charging characteristics can be programmed on the product
Application
Individually define the battery capacity needed –> see page 99
Protection for mains supply line in special cases only –> see page 104
Max. 38 Ah per battery charging unit (> 38 Ah = additional power supply)
Parallel operation of several battery charging units possible
Battery supply line has no EMI protection (battery cannot be removed)
CC11
Battery charging unit is integrated in the control panel module E3X10.
CI11
Battery charging plug-in module E3C011 needed
mains
Batteries
TF*
B2F020
FA...
29.6V
I-Bus
(mains voltage –> system voltage 29.6 V)
(capacityas required)
CI11
AlgoPilot
B3Q...
Power supply
mains
B2F020
E3C011
29.6V
I-Bus
008725_h_en_--
Batteries
FA...
TF*
95
06.2011

Hide quick links:

Advertisement

Table of Contents
loading