Siemens AlgoRex CS1140 Planning page 24

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

Outline quantities of C bus participants
reduce number
of nodes or use
an additional
station
number of
nodes < X ?
no
yes
select station with
higher capacity or
use an additional
station
number of
controls < X ?
no
yes
24
Building Technologies
Fire Safety & Security Products
New definition of the number of devices to count:
Structure
D bus participants with their own D bus address (e.g. DOT1151, DO1131, DM1154,
DCW1151, DOW1171...)
FDnet participants with their own FDnet address (e.g. DOOT2x1, DO2x1, DM2x1,
DS221 ....)
Every used input or output of a FDnet, interactive or AnalogPLUS line module
Example: DC1157 with 3 inputs –> 6 devices
DC1154 with 1 output and 1 input for confirmation message –> 4 devices
DCI222 with 4 inputs –> 8 devices
DCIO222 with 4 outputs and 4 inputs –> 16 devices
Purely logical controls: Every 'Control ELEMENT' or 'Control OBJECT' that is not di-
rectly linked to a channel
Collective lines (e.g. 1 line of the E3M080 plug-in module)
Inputs of plug-in modules (e.g. E3X10x –> I4, E3L020 –> I2, K3I110 –> LONin, external
LON device –> LONin))
Outputs of plug-in modules (e.g. E3X10x –> Q3, E3G050 –> Q1, K3I110 –> LONout,
external LON device –> LONout)
Parallel displays/mimic displays (equipped with up to 384 LEDs / relays)
Limitation in the logical structure
The limits of the logical structure depend on the node type, the highest possible CSX
number and the maximum number of digits on the display. These limits are provided by
the system and are not dependent on the size of memory.
'Limits of logical structure' table
Maximum number
Maximum number
AREAS
per
STATION
... 4
Maximum number of links in control objects 4 and 6 (RAM)
1 to 16 links can be programmed to activate control object 4 or 6.
Every link needs a particular volume of RAM.
The maximum number of links is therefore limited as shown in the following diagrams.
Important:
If controls are produced which span several CPUs (control object 6), all links must be
counted twice: Once in the control panel from which they originated and once in the
control panel to which they are linked.
Note:
In order to optimize the performance of your system, you must keep the number of
controls spanning several CPUs as low as possible.
Max. 40 controls spanning several CPUs (control object 6) are permitted per C bus.
Maximum number
SECTIONS
per
OBJECTS
AREA
... 255
Maximum number
per
ELEMENTS
SECTION
OBJECT
... 255
... 99
International
5: ...255
008725_h_en_--
Number
of devi-
ces
1
2
2
2
2
2
20
per
06.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents