Collective' Detector Line - Siemens AlgoRex CS1140 Planning

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

Line plug-in modules
26.7

'Collective' detector line

8 Stub lines
1
2
3
4
DBZ1197A
E3M080
5
8
70
Building Technologies
Fire Safety & Security Products
All detectors within a line have the same collective address (OBJECT)
Depending on application, end-of-line by means of transzorb diode or EOL22
(Ex)
Number of detectors per line:
DS11 detectors: Max. 25
MS6/7/9/24:
For detector types that can be activated, see compatibility overview (document
001260)
DJ1192
DO110x
DT110x
mixed detector series
DM1101
AT50
DMA1103
'old' detector series
DLO1191
DM1101
DMA1103
DLR11
no detectors permissible
DC1192
DO110x
24VDC
1) For details, see document 825 for MS6/7/9, for DS11 collective 001508
According to individual load factor
F716
F910
ATAN50
DF1191/92
DT110x
Restriction:
only with E3X100 permissible
see document 1204 and UP 109
DO1101-Ex
SB2
for details see document 1204
DO1101-Ex
SB3
1)
R970
'new' detector series
(DS11, MS9, MS716)
line termination :Transzorb 20 V
line resistance :max.150 
DM1101
DMA1103
'old' detector series
(MS712, MS6)
line termination EOL22
line resistance :max.250 
DO110x
DF1101-Ex
DT1101-Ex
Ex
DF1101-Ex
DT1101-Ex
Ex
008725_h_en_--
Line termination
EOL22 (Ex)
Line termination
EOL22 (Ex)
06.2011