Cc1142/43 In Housing H67 - Siemens AlgoRex CS1140 Planning

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

16

CC1142/43 in housing H67...

434
H67G601
1130
300
Control terminal installed separately
Comments:
- E3I020 if used mount
at position 32!
- B2F020 fits any
module space
If Z3I041 or B3P020 is
used, on Pos. 36
E3M060/071/171/120
and E3C011
not
possible!
Mounting of E3X10.:
Terminal block for
E3X10. containing in
cable set Z3I350 +
2 x Z1I030
EMC Precaution:
Relative to each
E3X10. and E3C011
module position, two
positions to the right
and two positions to
the left must
not be fit
with either E3I040 or
E3G080 modules
Building Technologies
Fire Safety & Security Products
H67G601/611:
Set with
- door
H67G611
- frame
- module chassis
- mains terminals
- battery supporting plate
- relay rail
B3Q...
H23B010
H23B040
B3Q321
Removable system control panel
With separate main CPU (E3X10.)
Separate connector panel
Space for options
Batteries: either 2x 12 V/24 Ah or 2x 12 V/38 Ah
Operating unit usually remote (can be fitted in doors)
Doors hinged on right with lock (DOM type)
Cable duct
01
02
03
04
Mains
terminals
1)
14
11
12
13
Z3I570
21
Cable duct
31
32
33
34
35
36
37
42
43
44
45
47
52
53
54
55
56
57
61
62
65
(Battery 12 V)
(Battery 12 V)
FA2006-A1
FA2006-A1
or
or
FA2007-A1
FA2007-A1
For details of H67... housing –> see section 22
For details of protective elements, modem filter –> see section 38, 29
Z1I070
or
Z1I040
Z1I050
or
Z1I110
Module
can be plugged
into connection block
B2F020
E3X10.
B3R051
Z3I350
04
- one or two connection cables Z1I070, Z1I040,
Z1I110 or Z1I050 are required for each module:
14
Line modules
LON module
Control modules
Extinguishing modules
Interfaces
One Z3I330 terminal block has space for:
either
- 2x Z1I050 or
- 8x Z1I070 or
38
37
- 4x Z1I040 or 4x Z1I110
Mains
terminals
- 1x Z1I050 and 2x Z1I040
1)
1) Protection elements, Modem filter
48
Special feature:
H67E100 has 3 different hole patterns for mounting.
58
As a result, the relationship between connection block /
modules / batteries can also be arranged differently
Important:
Comply with max. permissible number
of 'nodes' + I-Bus modules!
-> Details see chapter 'Outline quantities'
CC1142/43 in housing H67...
or
H67E101
FA...
FA...
Supplied with cabinet set H67G601/611
absolutely essential
recommended space allocation
41
008725_h_en_--
06.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents