Capacity Values For Standard Configurations - Siemens AlgoRex CS1140 Planning

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

36.3

Capacity values for standard configurations

CS1140 configuration
CI with 128 detectors interactive
(B3Q... + 1xE3M071 including detector + 1xE3G070 + 1xE3C011)
CI with 128 detectors AnalogPLUS
(B3Q... + 1xE3M111 including detector + 1xE3G070 + 1xE3C011)
CI with 16 lines collective
(B3Q... + 2xE3M080 including detector + 1xE3G070 + 1xE3C011)
TM
CI with 126 Sinteso
detectors (calculated using a load factor of 1)
(B3Q... + 1xE3M141 including detector + 1xE3G070 + 1xE3C011)
CC with 512 detectors interactive
(E3X102/103 + 1xB3Q... + 4xE3M071 including detectors + 2xE3L020)
CC with 512 detectors AnalogPLUS
(E3X102/103 + 1xB3Q... + 1xE3M111 including detectors + 2xE3L020)
CC with 64 lines collective
(E3X102/103 + 1xB3Q... + 8xE3M080 including detectors + 2xE3L020)
TM
CC with 252 Sinteso
detectors (calculated using a load factor of 1)
(E3X102/103 + 1xB3Q... + 1xE3M141 including detectors + 2xE3L020)
Example:
1) E3X102/103 + 1x B3Q... + 4x E3M071 including detectors + 2x E3L020 (120 mA + 100 mA + 460 mA + 44 mA = 724 mA)
2) 724 mA x 12 h x 1.25 x 1.1 = 11.9 Ah
3) 724 mA x 24 h x 1.25 = 21.7 Ah
4) 724 mA x 72 h = 52.1 Ah
5) For an accurate calculation, use document 008478 (Excel sheet)
Notes:
Fault signal acknowledged
LCD backlighting inactive (timeout expired)
Alarm devices, remote transmission devices etc. not considered
Alarming duration:
Alarming duration not considered (in most countries an alarming duration of 10... 30 min. still has to be considered with effectively con-
nected alarm devices), see chap. 36.2
Also consider quiescent current for extra battery charging plug-in module E3C011
Building Technologies
Fire Safety & Security Products
Quiescent
current
260 mA
235 mA
315 mA
284 mA
5)
(Example)
724 mA
1)
474 mA
944 mA
462 mA
5)
Emergency power supply
Battery capacity requirement for
12 h
24 h
4.2 Ah
7.8 Ah
18.7 Ah
3.8 Ah
7.0 Ah
16.9 Ah
5.1 Ah
9.4 Ah
22.6 Ah
4.7 Ah
8.5 Ah
20.4 Ah
11.9 Ah
21.7 Ah
52.1 Ah
2)
3)
7.8 Ah
14.2 Ah
34.1 Ah
15.5 Ah
28.3 Ah
67.9 Ah
7.6 Ah
13.8 Ah
33.3 Ah
008725_h_en_--
72 h
4)
101
06.2011