Emergency power supply
36.2
Quiescent current table
Component
Quiescent current at 24 V DC (typical)
B1F120 / B2F020 /
0
B2F040 / B2F060
B2Q191/B1Q101
33 mA
B3Q321
17 mA
B3Q440
25 mA
B3Q6../566
100 mA with inactive lighting (active = + 200 mA)
B3Q580
20 mA
B3Q590/595
18 mA
B3R051
22 mA
E3C011
50 mA
E3G050
10 mA
E3G060
25 mA
E3G070
25 mA
E3G080
35 mA
E3G091
0
E3G110
0
E3H021
85 mA
E3I020
25 mA
E3L020
22 mA
E3L030
18 mA
E3M060
155 mA (=120 mA + 0.7 mA per MS9i element)
E3M071
115 mA (=50 mA + 0.5 mA per D bus device)
E3M171
70 mA
E3M080
85 mA
E3M111
210 mA (=50 mA + 0.31 mA per D bus device)
E3M120
8.5 mA
E3M141
80 mA
E3X102/103
120 mA 'Horn' control line terminated
K1D012
25 mA
K1D081
50 mA
K1D121
50 mA
K1D140
25 mA
K1H022
20 mA
K3G060
6 mA
K3R072
22 mA
NK823x
190 mA
Z3B171
0
E3I040
15 mA
K3I050
15 mA
K3I090
50 mA
K3I110
24 mA
1) only valid for devices with APMK = 1 / IMK = 1 (value for devices > 1 multiplied). DC1151 example: 0.5 mA x 12 = 6 mA
100
Building Technologies
Fire Safety & Security Products
Quiescent current during battery operation (24 V)
–
As basis for individual emergency current calculation
–
The current of the 5 V supply is included in these values
–
all LEDs inactive
all relays inactive
all control lines connected
'Horn' control lines terminated
all lines terminated
all channels inactive
during degraded mode and alarm active only
(no external 24 V loading)
with 32 detectors (=50 mA without detectors + 0.5 mA
per D bus device)
37 mA + 6 mA per terminated line
(A+ no external 24 V loading)
+1.3 mA for each detector address
without devices (+0.47 mA per load factor)
(all LEDs and optocouplers active)
no external 24 V loading
max. 184 mA all rel. activated including service LED
Extra current during alarm
0
max. 1 A for duration of print process
+ 5 mA
+ 10 mA
+ 230 mA
+ 160 mA
+ 167 mA
+ 2 mA
per activated LED
0
+ 11 mA per activated relay
+ 23 mA per activated control line, no ext. load
+ 34 mA without external load (horns, etc.)
+ 25 mA without external load (valves, horns, etc.)
+ 9 mA
per activated channel
+ 15 mA per activated channel during degraded
mode
0
0
+ .. mA depending on what is activated
+ 40 mA no external load (FBF, HM, FSK)
1)
0
1)
0
0
1)
+ 10 mA per line in alarm
1)
0
0
+ .. mA depending on what is activated
+ 50 mA without external load (horns, etc.)
0
0
0
0
0
+ 3 mA
per relay
+ 2 mA
per activated LED (-> F50F410)
0
per activated relay (-> K3G060)
0
+ 27 mA per activated relay
0
+ 0 mA
or 4 mA per activated LED
0
+ 10 mA per activated relay
+ 0.5 mA per input with closed contact
008725_h_en_--