Quiescent Current Table - Siemens AlgoRex CS1140 Planning

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

Emergency power supply
36.2

Quiescent current table

Component
Quiescent current at 24 V DC (typical)
B1F120 / B2F020 /
0
B2F040 / B2F060
B2Q191/B1Q101
33 mA
B3Q321
17 mA
B3Q440
25 mA
B3Q6../566
100 mA with inactive lighting (active = + 200 mA)
B3Q580
20 mA
B3Q590/595
18 mA
B3R051
22 mA
E3C011
50 mA
E3G050
10 mA
E3G060
25 mA
E3G070
25 mA
E3G080
35 mA
E3G091
0
E3G110
0
E3H021
85 mA
E3I020
25 mA
E3L020
22 mA
E3L030
18 mA
E3M060
155 mA (=120 mA + 0.7 mA per MS9i element)
E3M071
115 mA (=50 mA + 0.5 mA per D bus device)
E3M171
70 mA
E3M080
85 mA
E3M111
210 mA (=50 mA + 0.31 mA per D bus device)
E3M120
8.5 mA
E3M141
80 mA
E3X102/103
120 mA 'Horn' control line terminated
K1D012
25 mA
K1D081
50 mA
K1D121
50 mA
K1D140
25 mA
K1H022
20 mA
K3G060
6 mA
K3R072
22 mA
NK823x
190 mA
Z3B171
0
E3I040
15 mA
K3I050
15 mA
K3I090
50 mA
K3I110
24 mA
1) only valid for devices with APMK = 1 / IMK = 1 (value for devices > 1 multiplied). DC1151 example: 0.5 mA x 12 = 6 mA
100
Building Technologies
Fire Safety & Security Products
Quiescent current during battery operation (24 V)
As basis for individual emergency current calculation
The current of the 5 V supply is included in these values
all LEDs inactive
all relays inactive
all control lines connected
'Horn' control lines terminated
all lines terminated
all channels inactive
during degraded mode and alarm active only
(no external 24 V loading)
with 32 detectors (=50 mA without detectors + 0.5 mA
per D bus device)
37 mA + 6 mA per terminated line
(A+ no external 24 V loading)
+1.3 mA for each detector address
without devices (+0.47 mA per load factor)
(all LEDs and optocouplers active)
no external 24 V loading
max. 184 mA all rel. activated including service LED
Extra current during alarm
0
max. 1 A for duration of print process
+ 5 mA
+ 10 mA
+ 230 mA
+ 160 mA
+ 167 mA
+ 2 mA
per activated LED
0
+ 11 mA per activated relay
+ 23 mA per activated control line, no ext. load
+ 34 mA without external load (horns, etc.)
+ 25 mA without external load (valves, horns, etc.)
+ 9 mA
per activated channel
+ 15 mA per activated channel during degraded
mode
0
0
+ .. mA depending on what is activated
+ 40 mA no external load (FBF, HM, FSK)
1)
0
1)
0
0
1)
+ 10 mA per line in alarm
1)
0
0
+ .. mA depending on what is activated
+ 50 mA without external load (horns, etc.)
0
0
0
0
0
+ 3 mA
per relay
+ 2 mA
per activated LED (-> F50F410)
0
per activated relay (-> K3G060)
0
+ 27 mA per activated relay
0
+ 0 mA
or 4 mA per activated LED
0
+ 10 mA per activated relay
+ 0.5 mA per input with closed contact
008725_h_en_--
06.2011