LON bus devices
28
LON bus devices
28.1
Features
28.2
LON bus as stub line
E3X10.
or
B3Q...
Z1I100/110
E3I040
78
Building Technologies
Fire Safety & Security Products
Activation via local 'LON' communication bus
4 different device types
B3Q580
=
–
B3Q590/595
=
–
K3I050
=
–
K3I110
=
–
Activation via LON plug-in module E3I040 (converter between I bus and LON
bus)
The 'LON bus' function is available once per 'CI' / 'CT' and 'CC' station type
Max. 32 devices per LON bus (device types can be mixed in any way)
Monitored two-wire bus without loop line function
All devices require a separate supply line as of E3I040
LON bus line management
As 'Stub line' up to 1000 m (without T-branches)
–
As 'Free topology' up to 500 m (length of line to all devices added together)
–
(with
'MICC'
'Free
topology'
With special cable (Belden 85102 or 8471) and as 'Stub line' up to 2700 m
–
Possible via twisted line only (twisted in pairs, 10 twists a meter)
–
CPU-wide functions possible
B3Q59x: 3 LEDs can be replaced. Permits application with different LED color.
I-Bus
E3I040
LON-Bus
Z1B070
plain text display terminal
plain text operating terminal
LON/mimic display converter
LON I/O board
: as
'Stub
...300
m)
max. length of LON-Bus 1000m
24VDC
K3I110
K3I050
24VDC
For details see
K3R072 –> page 76 or
B3R051 –> page 51
E3I040
line'
....700
m
B3Q590/
B3Q580
(not monitored)
Data bus
K3R072
or
B3R051
008725_h_en_--
/
as
CC11
CI11
CT11
595
K3R072
or
B3R051
06.2011