Programming

5.8 Parameter STATUS

5.8
Parameter STATUS
The following table shows the explanation of each STATUS value:
● When the value of STATUS is greater than 16#80: It shows the detailed error code.
● When the value of STATUS is less than 16#80: It indicates the progress of the function
block.
Table 5- 8
STATUS message
Value of STATUS
16#00
16#01~16#7E
16#7F
16#82
16#83
16#84
16#85
16#87
16#88
16#89
16#8A
16#8B
16#8C
16#8D
16#8E
16#8F
16#90
16#91
16#F0
106
Explanation
The function block is not started.
For the detailed description, refer to each function block.
The function block is completed successfully and the output parameters are ready.
The CM 1xDALI is busy with the last command.
Timeout. The function block does not get the response from CM 1xDALI.
Cancel. The function block is cancelled by command.
CM 1xDALI receives an error response frame after sending the query command. This might be
caused by a short address confliction or a DALI device failure.
Note: Not every short address conflict can be detected. It can only be detected when the conflict-
ed devices send the response frame at the same time.
Not supported. This action is not supported by CM 1xDALI.
Invalid parameters. The input of the function block is not correct.
No data. There is no data saved in CM 1xDALI or no response on the DALI bus.
Status error. The CM 1xDALI is not in the normal state. For the detailed information, refer to the
output "STATUS" of DALI_CTRL (Page 26).
Configuration mismatch. The actual device is not matched with the control gear or input device
(sensor) which is added by DALI_ECG_ADD (Page 67) or DALI_SENSOR_ADD. (Page 89)
The short address is not configured, and there is no device with this short address on the DALI
bus.
No device is configured with this short address.
No physical device with the specified short address is on the DALI bus.
The scan procedure is stopped abnormally.
CM 1xDALI cannot send commands to the DALI bus.
The input type of control gear or input device (sensor) is not matched with the physical device.
Communication failure between CPU and CM 1xDALI.