5.3
FB error messages
5.3.1
Structure of the status output parameter
There is always an error status in the Ident profile function if the output parameter
ERROR = TRUE. The error can be analyzed (decoded) using the STATUS output
parameter.
The STATUS output parameter is made up of 4 bytes:
Byte
Byte 0
Byte 1
Byte 2
Byte 3
Communications module RF120C with application blocks for S7-1200 and S7-1500
Operating Instructions, 07/2013, C79000-G8976-C328-01
Meaning
Function numbers
Cx - error in bus communication (backplane bus, PROFINET,
•
PROFIBUS)
E1 - transponder-related error
•
E2 - error on the air interface
•
E4 - reader hardware fault
•
E5 - error in the communication between reader and FB
•
E6 - error in the user command
•
E7 - error message generated by the FB
•
Error numbers
This byte defines the meaning of the error code and the warnings. The error
numbers have the followinig meaning:
0x00 - no error, no warning
•
0x80 - error message from the backplane bus or from PROFIBUS DP-V1
•
or PROFINET (in accordance with IEC 61158-6)
0x81 ... 0x8F - the controller reports an error according to the parameter
•
"x" (0x8x).
0xFE - error from the Ident profile or communications module/reader
•
Error code
Warnings
In this byte, each bit has a separate meaning.
Service and maintenance
5.3 FB error messages
51