Siemens SIMATIC ET 200SP CM 1xDALI Manual page 67

Communication module
Hide thumbs Also See for SIMATIC ET 200SP CM 1xDALI:
Table of Contents

Advertisement

Programming
5.6 Diagnostic function blocks
Parameter
The following table shows the parameters of the function block:
Parameter
Declaration
CHECK
Input
STATUS_
MASK
CM_DALI
InOut
BUSY
Output
ACTIVE
DONE
ERROR
STATUS
MATCH
66
Data type
Memory
area
BOOL
I, Q, M, D,
Compare the specified status mask with sensors upon a rising edge.
L or Con-
stant
Ar-
I, Q, M, D,
Show the status mask of all the sensors.
ray[0..63]
L or Con-
of BYTE
stant
"DALI_CT
The data block of DALI_CTRL specifies the CM 1xDALI which com-
RL"
municates with the current function block.
BOOL
I, Q, M, D,
Status parameter:
L
BOOL
I, Q, M, D,
Status parameter:
L
BOOL
I, Q, M, D,
Status parameter:
L
BOOL
I, Q, M, D,
Status parameter:
L
BYTE
I, Q, M, D,
When ERROR = 0, STATUS has
L
following three values:
Ar-
I, Q, M, D,
Check result of devices on all the short addresses.
ray[0..63]
L
MATCH = 1: The status of the sensor which is matched with the speci-
of BOOL
fied status mask.
The index of the array indicates the short address.
BUSY = 0: Processing of job is terminated.
BUSY = 1: Job is still being committed.
ACTIVE = 0: Job is not yet started.
ACTIVE = 1: Job is being executed.
DONE = 0: Job is not yet started or still executing.
DONE = 1: Job is executed without errors.
ERROR = 0: No error occurs.
ERROR = 1: Error occurs during processing.
16#00: Idle
16#01: Executing
16#7F: Completed
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Description
When ERROR = 1, STATUS
shows the detailed error code. For
the detailed meaning of each
error code, refer to Parameter
STATUS (Page 106).
Manual, 06/2019, A5E46959434-AA