Dali_Ecg_Delete - Siemens SIMATIC ET 200SP CM 1xDALI Manual

Communication module
Hide thumbs Also See for SIMATIC ET 200SP CM 1xDALI:
Table of Contents

Advertisement

5.7.2

DALI_ECG_DELETE

Description
DALI_ECG_DELETE is used for deleting one configured control gear.
This function block does not send any command to the DALI bus, but deletes the device
which is added by using DALI_ECG_ADD (Page 67) and the data which is saved in the CM
1xDALI (refer to data flow path 1 (Page 23)).
Parameter
The following table shows the parameters of the function block:
Parameter
Declaration
DELETE
Input
ADDRES
S
CM_DALI
InOut
BUSY
Output
ACTIVE
DONE
ERROR
STATUS
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
Data type
Memory
area
BOOL
I, Q, M, D,
Delete one configured control gear upon a rising edge.
L or Con-
stant
USInt
I, Q, M, D,
Specify the short address of the device.
L or Con-
Range: 0 to 63
stant
"DALI_CT
The data block of DALI_CTRL specifies the CM 1xDALI which com-
RL"
municates with the current function block.
BOOL
I, Q, M, D,
Status parameter:
L
BOOL
I, Q, M, D,
Status parameter:
L
BOOL
I, Q, M, D,
Status parameter:
L
BOOL
I, Q, M, D,
Status parameter:
L
BYTE
I, Q, M, D,
When ERROR = 0, STATUS has
L
following three values:
BUSY = 0: Processing of job is terminated.
BUSY = 1: Job is still being committed.
ACTIVE = 0: Job is not yet started.
ACTIVE = 1: Job is being executed.
DONE = 0: Job is not yet started or still executing.
DONE = 1: Job is executed without errors.
ERROR = 0: No error occurs.
ERROR = 1: Error occurs during processing.
16#00: Idle
16#01: Executing
16#7F: Completed
5.7 Configuration function blocks
Description
When ERROR = 1, STATUS
shows the detailed error code. For
the detailed meaning of each
error code, refer to Parameter
STATUS (Page 106).
Programming
69

Hide quick links:

Advertisement

Table of Contents
loading