5.7.11

DALI_SENSOR_ADD

Description
DALI_SENSOR_ADD is used for adding or modifying one configured sensor, including its
instances.
● In order to add one configured sensor, you must set the sensor type of the instance.
● The total number of instances within all sensors which you can add is limited to 64. If the
total number of instance exceeds the limitation, this function block returns an error of
16#87 (not supported).
● This function block does not send any command to the DALI bus, and the CM 1xDALI
saves the data of the added devices (refer to data flow path 1 (Page 23)).
● After adding the device using this function block, the parameters you set using other
function blocks (for example, DALI_SENSOR_SET_DEV_PARAM (Page 93) and
DALI_SENSOR_SET_INST_PARAM (Page 97)) are saved in the CM 1xDALI.
● The device is marked as configured after the device type is set. Refer to the output
CONFIGURED of function block DALI_DEV_QUERY_ADDR (Page 37).
● All the setting parameters are saved in the CM 1xDALI until the device is deleted by using
DALI_SENSOR_DELETE (Page 91) or reset by using DALI_DEV_RESET (Page 104).
ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
Programming
5.7 Configuration function blocks
89