Chapter 7: Specifications - Vertiv Liebert GXT5 Series Installer/User Manual

120 v input, 120 v output
Hide thumbs Also See for Liebert GXT5 Series:
Table of Contents

Advertisement

Chapter 7: Specifications

Table 7-1 UPS Specifications, 500 VA to 1000 VA models
MODEL GXT5-
Dimensions, D×W×H, in. (mm)
Unit
Shipping
Weight, lb.(kg)
Unit
Shipping
Input AC
Voltage Range (typical)
90% ~ 100% loading
70% ~ 90% loading
50% ~ 70% loading
0% ~ 50% loading
Frequency
Input Power Cord
Output AC
Output Receptacles
Voltage
Waveform
Normal Mode Overload
Battery Parameters
Type
Quantity x Voltage x Rating
Battery Mfr�/Part #
Back-up time
Recharge time
Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Relative Humidity
Operating Elevation
Audible Noise
Agency
Surge Immunity
Transportation
Vertiv | Liebert® GXT5™ | Installer/User Guide
500LVRT2UXL
RATING
500 VA/500 W
<46 dBA max� at 3 ft (1 m) front and sides, <43 dBA max� at 3 ft (1 m) rear
750LVRT2UXL
750 VA/750 W
15�7 x 16�9 x 3�4 (400 x 430 x 85)
24�3 x 22�4 x 10�3 (617 x 570 x 262)
37 (16�8)
49�9 (22�68)
120 VAC nominal, variable based on output load
94 ~ 102 VAC/149�5 VAC
77 ~ 94 VAC/149�5 VAC
60 ~ 77 VAC/149�5 VAC
60 VAC/149�5 VAC
40 Hz ~ 70 Hz; auto-sensing
10-ft� (3 m) attached with NEMA 5-15P plug
5-15R x 6
100/110/115/120/125 VAC (user-configurable); ±3%
Sine wave
> 200% for 250 mS
150 - 200% for 2 seconds
125 - 150% for for 60 seconds
Valve-regulated, non-spillable, lead acid
3 x 12V x 9�0AH
LEOCH DJW12-9�0
See
Battery Run Times
3 hours to 90% capacity
32 to 122 (0 to 50)
–4 to 140 (–20 to 60) [batteries are from 5 to 104 (–15 to 40)]
0% – 95% non-condensing
Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating
IEEE/ANSI C62�41 Category B (6kV/3kA)
ISTA Procedure 1A
1000LVRT2UXL
1000 VA/1000 W
on
page
70�
67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents