Vertiv Liebert GXT5 Series Installer/User Manual page 45

120 v input, 120 v output
Hide thumbs Also See for Liebert GXT5 Series:
Table of Contents

Advertisement

IT system compatibility
When this option is enabled, the "Input phase reversed" and "Input ground lost" alarms are disabled�
• Enable
• Disable (default)
Outlet Parameter Options
Apply the same settings as outlet 1
Available on outlets 2 through 4, this applies the settings for Outlet1 to this outlet� This lets you apply the
settings for Outlet1 and apply identical settings to any other programmable outlet�
Turn on/off outlet
Turns on or turns off the outlet based on the current state� Provides a confirmation window with Yes/No
options to confirm turning on the outlet�
Turn on delay
Length of time before outlet turns on after UPS start-up�
• 0 to 30 minutes (default is 0)
Turn off when UPS overloads
Sets whether or not to turn off the outlet if the UPS is overloaded while on battery power� This can be
used to disable lower priority equipment in the event of an overload while in battery mode�
• Yes
• No (default)
Outlet settings based on discharging time
Threshold of turning off the outlet
Length of time that the outlet is powered after the batteries begin to discharge� Select the checkbox to
enable or disable (default) the option�
• 0 to 30 minutes (default is 5)
Turn on when power returns for
Length of time after the mains input power returns before turning on the outlet� Select the checkbox to
enable (default) or disable the option�
• 0 to 30 minutes (default is 5)
Outlet settings based on backup time
Threshold of turning off the outlet
When the selected amount of time remains on battery mode, the outlet is turned off� Select the checkbox
to enable or disable (default) the option�
• 0 to 30 minutes (default is 5)
40
Operation and Display Panel