Chapter 2: Installation

Do not start the UPS until after the installation is finished�
WARNING! Risk of electric shock
Can cause equipment damage, injury and death. Before beginning installation, verify that all external overcurrent
protection devices are open (Off), and that they are locked-out and tagged appropriately to prevent activation
during the installation, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved
personal protective equipment (PPE) per NFPA 70E. Failure to comply can cause serious injury or death. Before
proceeding with installation, read all instructions. Follow all local codes.
2.1. Unpacking and Inspection
Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage� If any shipping damage is found, report it to the carrier and your local
Vertiv representative immediately�
• Check the accessories included against the packing list� If there is any discrepancy, contact your local Vertiv
representative immediately�
CAUTION
The UPS is heavy (see
moving the unit.
2.2. Pre-installation Preparation
• Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off� The installation
environment should meet the specifications listed in
• Place the UPS in an area of unrestricted air-flow around the unit, away from water, flammable liquids, gases,
corrosives, and conductive contaminants� Avoid direct sunlight�
NOTE: Operating the UPS in temperatures above 77°F (25°C) reduces battery life.
2.2.1. Installation Clearances
Maintain at least 4 in� (100 mm) clearance in the front and rear of the UPS� Do not obstruct the air inlets on the
front panel and rear panel of the UPS� Blocking the air inlets reduces ventilation and heat dissipation, shortening
the service life of the unit�
Vertiv | Liebert® GXT5™ | Installer/User Guide
Specifications
on
page
57, for the weight). Take proper precautions when lifting or
Specifications
on
page
57�