Remote control
Allows the UPS to be controlled remotely via the CLI or RDU101 card�
• Enable (default)
• Disable
Any mode shutdown auto restart enable
Automatically restart the UPS after an "Any mode shutdown" signal is received� When the UPS is shut down
via dry-contact inputs 1 or 2, it will restart automatically if this option is enabled�
• Enable
• Disable (default)
Output contact NO/NC
Selects the states of the dry contact outputs 5 and 6�
• Normally open (default)
• Normally closed
Input contact NO/NC
Selects the states of the dry contact inputs 1 and 2�
• Normally open (default)
• Normally closed�
Dry contact 5 (Output)
Selects the output of dry-contact 5�
• Low battery = The contacts switch when the UPS reaches the amount of time left on battery
configurable from "Low battery time"� (default)
• On bypass = The contacts switch when the UPS is running in bypass mode
• On battery = The contacts switch when the UPS is running on battery
• UPS fault = The contacts switch when a UPS fault has occurred
Dry contact 6 (Output)
Selects the output of dry contact 6�
• Low battery = The contacts switch when the UPS reaches the amount of time left on battery
configurable from "Low battery time"�
• On bypass = The contacts switch when the UPS is running in bypass mode
• On battery = The contacts switch when the UPS is running on battery
• UPS fault = The contacts switch when a UPS fault has occurred� (default)