Vertiv Liebert GXT5 Series Installer/User Manual page 42

120 v input, 120 v output
Hide thumbs Also See for Liebert GXT5 Series:
Table of Contents

Advertisement

Audible alarm
If enabled, the UPS will beep when an alarm is generated� If disabled, it will be silent� See
(Buzzer)� on
page
69�
• Enable (default)
• Disable
Change settings password
Opens the dialog to change the password used to access and update the UPS parameter settings, see
Changing the Password
System Parameter Options
Auto restart
Allows the automatic restart of the UPS when input power is restored after a complete shutdown of the UPS
system�
• Enable = The UPS will restart automatically when the input power is restored after a complete shut
down� (default)
• Disable = The UPS will not restart automatically
Auto restart delay
Length of time to elapse before an automatic restart after input power is restored�
• 0 - 999 seconds (default 0)
Guaranteed shutdown
Forces a continued shutdown of the UPS once the Low Battery threshold is reached, even if input power is
restored during this time� This can be used to make sure that connected equipment shuts down completely� When
using the low battery relay output to gracefully shut down connected equipment, it is possible that the input power
is restored after the Low battery output is triggered� In this situation, the connected equipment could power down
smoothly but never lose input power, causing it not to start back up as intended� Enabling this option prevents this
situation from occurring by ensuring that a shutdown of the output happens�
• Enable (default)
• Disable
Start with no battery
Allows the UPS to start when the battery has reached the end of discharge (EOD)� This can be used to turn
on the UPS and power the attached load without battery protection when utility power has been restored after the
battery was fully depleted� It works in conjunction with the Auto restart setting above�
• Enable (with Auto restart enable) = The UPS will power the load with no user intervention when
mains power returns after the battery has been fully depleted
• Enable (with Auto restart disabled) = The UPS will start up and allow the user to turn on the output
when power returns after the battery has been fully depleted
• Disable = The UPS cannot start with a fully depleted battery (default)
Vertiv | Liebert® GXT5™ | Installer/User Guide
on
page
48�
Audible Alarm
37