2.5. Connecting AC Input Power
Ensure that all the loads are turned Off� Prepare an input power supply that is properly protected by a circuit breaker
in accordance with national and local electrical codes� The wall receptacle must be grounded� We recommend
installing an upstream circuit breaker of the same series as the input circuit breaker of the GXT5�
Table 2-1
below, lists the specifications of the input circuit breaker on the rear panel by UPS model�
To connect AC-input power, plug the input plug of the UPS into the input-power connection�
NOTE: If the input plug will serve as the disconnecting device, the wall socket/outlet must be near the UPS and
must be easily accessible, per the National Electric Code/NFPA 70 requirements.
A. Connecting Loads
500-VA to 1500-VA models have six outlets:
• Two are not programmable (always On)�
• Four are controlled with programmed responses or an SNMP network�
2000-VA and 3000-VA models have seven outlets:
• Three are not programmable (always On)�
• Two groups are controlled with programmed responses or an SNMP network�
NOTE: When connecting load, verify that the equipment is plugged into the appropriate outlets if any of the
outlets will be controlled. Do not overload any output receptacle. Output cable length should not exceed 10
m (32.8 ft).
To connect equipment, plug equipment into the appropriate output receptacles on the rear of the UPS, see the
appropriate figure for your model in
Vertiv | Liebert® GXT5™ | Installer/User Guide
Table 2-1 Input circuit breaker specifications
MODEL
GXT5-500LVRT2UXL
GXT5-750LVRT2UXL
GXT5-1000LVRT2UXL
GXT5-1500LVRT2UXL
GXT5-2000LVRT2UXL
GXT5-3000LVRT2UXL
Rear Panels
on
page
4�
RATED CIRCUIT BREAKER
12 A
12 A
12 A
15 A
20 A
30 A
15