2�6� Communication Connections; 2�6�1� Connecting Intellislot Communication; 2�6�2� Connecting To The Dry-Contact Port - Vertiv Liebert GXT5 Series Installer/User Manual

120 v input, 120 v output
Hide thumbs Also See for Liebert GXT5 Series:
Table of Contents

Advertisement

2.6. Communication Connections
The UPS offers several communication interfaces and ports�
NOTE: We recommend that signal-cable lengths be less than 10 ft (3 m), and are kept away from power
cabling.
2.6.1. Connecting IntelliSlot Communication
The Liebert® IntelliSlot™ RDU101 provides SNMP monitoring of the UPS across the network and/or building
management system�
See the appropriate figure for your model in
Rear Panels
on
page
4, for the location of the card port�
To install an IntelliSlot Card:
1� Remove the screws from the slot cover plate and remove the plate�
2� Insert the card into the slot, and secure with the screws that held the cover plate�
To make connections to the card, refer to the Installer/User Guide for the appropriate IntelliSlot card available at
www�vertiv�com�
2.6.2. Connecting to the Dry-contact Port
The UPS includes a dry-contact port� See the appropriate figure for your model in
Rear Panels
on
page
4, for
the location of the port�
Figure 2-3
below, shows the ports and
Table 2-2
on the next page, describes each port�
The I/O dry contact port capacity is 125 Vac, 0�5 A; 30 Vdc, 1 A�
Figure 2-3 Dry-contact Port and Pin Layout
NOTE: Pins 7 and 8 are shorted before delivery.
16
Installation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents