Vertiv Liebert GXT5 Series Installer/User Manual page 73

120 v input, 120 v output
Hide thumbs Also See for Liebert GXT5 Series:
Table of Contents

Advertisement

Table 7-2 UPS Specifications, 1500 VA to 3000 VA models
MODEL GXT5-
Dimensions, D×W×H, in. (mm)
Unit
Shipping
Weight, lb.(kg)
Unit
Shipping
Input AC
Voltage Range (typical)
90% ~ 100% loading
70% ~ 90% loading
50% ~ 70% loading
0% ~ 50% loading
Frequency
Input Power Cord
Output AC
Output Receptacles
Voltage
Waveform
Normal Mode Overload
Battery Parameters
Type
Quantity x Voltage x Rating
Battery Mfr�/Part #
Back-up time
Recharge time
Environmental
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Relative Humidity
Operating Elevation
Audible Noise
Agency
Surge Immunity
Transportation
68
1500LVRT2UXL
RATING
1500 VA/ 1350 W
18�5 x 16�9 x 3�4 (470 x 430 x 85)
24�3 x 22�4 x 10�3 (617 x 570 x 262)
46�2 (21)
57�4 (26�1)
10-ft� (3 m) attached with
NEMA 5-15P plug
5-15R x 6
> 200% for 250 mS
150 – 200% for 2 seconds
125 – 150% for for 50 seconds
105 – 125% for 60 seconds
4 hours to 90% capacity after full discharge with 100% load
till UPS auto-shutdown (internal batteries only)
<46 dBA max� at 3 ft (1 m) front and sides, <45 dBA max� at
2000LVRT2UXL
2000 VA/ 1800 W
47�5 (21�6)
58�7 (26�7)
120 VAC nominal, variable based on output load
94 ~ 102 VAC/149�5 VAC
77 ~ 94 VAC/149�5 VAC
60 ~ 77 VAC/149�5 VAC
60 VAC/149�5 VAC
40 Hz ~ 70 Hz; auto-sensing
10-ft� (3 m) attached with
NEMA L5-20P plug
L5-20R + 5-15/20R x 6
100/110/115/120/125 VAC (user-configurable); ±3%
Sine wave
Valve-regulated, non-spillable, lead acid
4 x 12V x 9�0AH
LEOCH DJW12-9�0
See
Battery Run Times
32 to 122 (0 to 50)
–4 to 140 (–20 to 60) [batteries are from 5 to 104 (–15 to 40)]
0% – 95% non-condensing
Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating
3 ft (1 m) rear
IEEE/ANSI C62�41 Category B (6kV/3kA)
ISTA Procedure 1A
3000LVRT2UXL
3000 VA/ 2700 W
21�3 x 16�9 x 3�4
(540 x 430 x 85)
28�2 x 22�4 x 10�3
(717 x 570 x 262)
66 (30)
77�2 (35�1)
10-ft� (3 m) attached with NEMA L5-30P
plug
L5-30R + 5-15/20R x 6
> 200% for 250 mS
150 – 200% for 2 seconds
125 – 150% for for 10 seconds
105 – 125% for 15 seconds
6 x 12V x 9�0AH
on
page
70�
3 hours to 90% capacity after full
discharge with 100% load til UPS auto-
shutdown (internal batteries only)
<46 dBA max� at 3 ft (1 m) front and sides,
<48 dBA max� at 3 ft (1 m) rear
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents