Network Devices - BRP I-Command Evinrude Etec Series User Manual

Table of Contents

Advertisement

Network Devices

Also see the "Network Specification Diagram" on page 10.
Buss Length
The distance between any two points on the network must not exceed 100 meters (328 ft.).
Measure the distance from the Tee-connector to the last device at each end of the network. Device cable
lengths at the ends of the network must be included in the total network buss length calculation.
Devices
Devices may be installed in any order. When installing temperature, pressure and fluid level sensors, install
one device at a time. Configure the device, see "Advanced Setup and Operation" on page 57, then repeat this
process for each sensor device being installed.
Device Cable Lengths
•Must not exceed 6 meters (19 ft.) for single device cable lengths
•Must not exceed 78 meters (256 ft.) for total device cable lengths
Maximum Number of Devices
A maximum of 50 devices can be attached to a network.
IMPORTANT: There should be no "open" or unused network device connectors. Remove unused network
device connectors.
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents