Installing the new streaming and recording server
Temperature and humidity requirements
The following table lists the temperature and humidity requirements for the server.
Specification
Temperature range
Operating
Non-operating
Relative humidity (non-condensing)
Operating
Non-operating
Related links
Physically connecting the new server
Power requirements
The following table lists the power requirements for the server.
Table 7: HP 800 W CS power supply (92% efficiency)
Specification
BTU
Voltage
Plug Type
Circuit Breaker
Pole
AMP Draw
Total Watts
Note:
These numbers are based on the following typical Avaya configuration:
• qty=2 – E5-2620v3 six core processors
• qty=8x4 GB – Memory (1Rx4 PC4-2133P –R Kit)
• qty=3 – 2.5" SFF SAS HDDs
August 2017
Value
Note:
All temperature ratings shown are for sea level. An altitude derating of
1°C per 304.8 m (1.8° per 1,000 ft.) above sea level to a maximum of
3048 m (10,000 ft), no direct sustained sunlight.
10° to 35°C (50° to 95°F) Maximum rate of change is 20°C/hr (36°F/hr).
The upper limit might be limited by the type and number of options installed.
System performance may be reduced if operating with a fan fault or above
30°C (86°F).
-30° to 60°C (-22° to 140°F). Maximum rate of change is 20°C/hr (36°F/hr).
8 to 90% relative humidity (Rh), 24°C (75.2°F) maximum wet bulb
temperature, non-condensing.
5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb
temperature, non-condensing.
on page 26
Installing the Avaya Equinox Streaming and Recording Server
Comments on this document? infodev@avaya.com
Value
917 BTU/hr
100V — 240V
NEMA — 15
15 Amp
1
2.7 @ 100VAC
269 W
42