Heating Circuit 1", "Heating Circuit 2", "Heating Circuit 3" Group; Coding - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

Coding level 2
"Solar" group
(cont.)
Coding in the delivered condition
27:15
Cyclical heating time 15 min
Once the DHW cylinder with priori-
ty is heated up, the DHW cylinder
without priority is heated for a max-
imum duration equal to the set cy-
clical heating time.
28:3
Cyclical pause time 3 min.
After the selected cyclical heating
time for the DHW cylinder without
priority has expired, the rise in col-
lector temperature is captured dur-
ing the cyclical pause time.

"Heating circuit 1", "Heating circuit 2", "Heating circuit 3" group

Coding

Coding in the delivered condition
A0:0
Without remote control
A1:0
Only with Vitotrol 200A:
All settings available on the remote
control can be carried out.
A2:2
Cylinder priority control for heating
circuit pump and mixer
A3:2
Outside temperature below 1 °C:
Heating circuit pump "ON"
Outside temperature above 3 °C:
Heating circuit pump "OFF"
!
Please note
With settings below 1 °C there is a risk that pipes outside the thermal envelope of the house could freeze
up.
Standby mode in particular should be taken into consideration, e.g. during holidays.
Parameter
Address A3:...
9
8
7
6
5
4
50
Possible change
27:5
to
27:60
28:1
to
28:60
Possible change
A0:1
A0:2
A1:1
A2:0
A2:1
A2:3
to
A2:15
A3:–9
to
A3:15
Heating circuit pump
"On"
10 °C
9 °C
8 °C
7 °C
6 °C
5 °C
The cyclical heating time is adjusta-
ble from 5 to 60 min.
Cyclical pause time is adjustable
from 1 to 60 min.
With Vitotrol 200A or
Vitotrol 200 RF; automatic recogni-
tion.
With Vitotrol 300A or
Vitotrol 300 RF; automatic recogni-
tion.
Only party mode can be set at the
remote control.
Without cylinder priority for heating
circuit pump and mixer
Cylinder priority only for mixers
Modulating priority for mixers, i.e.
the heating circuit receives a re-
duced amount of heat.
Heating circuit pump "ON/OFF" (see
the following table)
"Off"
8 °C
7 °C
6 °C
5 °C
4 °C
3 °C

Hide quick links: