Coding level 2
"General" group
(cont.)
Coding in the delivered condition
8F:0
Operation enabled in standard
menu and in extended menu.
Note
The respective code is only activa-
ted when you exit the service
menu (see page 55).
8 A:175
Do not adjust
90:128
Time constant for calculating the
adjusted outside temperature
21.3 h
95:0
Without communication interface
Vitocom 100, type GSM
97:0
With LON communication module:
The outside temperature of the
sensor connected to the control
unit is used internally.
98:1
Viessmann system number (in
conjunction with monitoring several
systems via Vitocom 300).
9b:70
Set minimum boiler water tempera-
ture during external demand 70 °C
9C:20
LON subscriber monitoring
If there is no response from a sub-
scriber for 20 min, the values
specified in the control unit are
used. Only then will a fault mes-
sage be issued.
9F:8
Only for heating circuits with mixer:
Differential temperature 8 K

"Boiler" group

Coding

Coding in the delivered condition
02:0
Single-stage burner
03:0
Do not adjust
04:0
Burner switching hysteresis 4 K
44
Possible change
8F:1
Operation blocked in standard menu
and in extended menu.
Emissions test mode can be ena-
bled.
8F:2
Operation enabled in standard
menu, blocked in extended menu.
Emissions test mode can be ena-
bled.
90:1
Subject to the set value, the flow
to
temperature is adjusted quickly (low
90:199
values) or slowly (high values) when
the outside temperature changes.
1 step
95:1
With communication interface
Vitocom 100, type GSM; automatic
recognition.
97:1
The control unit receives the outside
temperature.
97:2
The control unit sends the outside
temperature to the Vitotronic 200-H.
98:1
System number adjustable from 1 to
to
5.
98:5
9b:0
Set value adjustable from 0 to
to
127 °C.
9b:127
9C:0
No monitoring
9C:5
Time adjustable from 5 to 60 min
to
9C:60
9F:0
Differential temperature adjustable
to
from 0 to 40 K.
9F:40
Possible change
02:1
Two-stage burner
02:2
Modulating burner
04:1
Burner switching hysteresis is heat
demand-dependent:
ERB50 function (values from 6 to
12 K)
04:2
Burner switching hysteresis is heat
demand-dependent:
10 min