Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 45

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

"Boiler" group
(cont.)
Coding in the delivered condition
06:74
Electronic maximum limit for boiler
water temperature set to 74 °C.
Note
The code has no effect during
DHW heating demand.
0b:0
Do not adjust
10:20
Hook-up delay for enabling stage 2
in addition to stage 1 during heat-
ing operation (integral) = 2560 Ks
11:20
Hook-up delay for enabling stage 2
in addition to stage 1 during cylin-
der heating (integral) = 2560 Ks
12:20
Shutdown delay for blocking stage
1 in addition to stage 2 (integral) =
2560 Ks
13:6
Shutdown differential 6 K
The burner shuts down when the
set boiler water temperature is ex-
ceeded.
15:15
Do not adjust
16:6
Modulating burner offset during
start optimisation 6 K
17:120
Modulating burner control amplifi-
cation 12 %/K
18:30
Modulating burner integral action
time 300 s
1A:6
Duration of the start optimisation
for modulating burner 6 min
1C:120
Signal B4 at plug
Compensation of signal delay for
hours run meter. Time from initia-
tion of burner start signal at T2 in
plug
fA
valve. At each burner start, 120 s
will be taken off the runtime.
1F:0
With flue gas temperature sensor:
Flue gas temperature is not moni-
tored for burner service indication
21:0
No service interval (hours run) se-
lected.
not available:
fA
to opening of the solenoid
Possible change
ERB80 function (values from 6 to
20 K)
06:20
Maximum limit adjustable from 20 to
to
127 °C.
06:127
Note
Observe the " " temperature con-
troller setting (see page 13)
10:0
Hook-up delay adjustable from 0 to
to
25,472 Ks.
10:199
1 step
11:0
Hook-up delay adjustable from 0 to
to
25,472 Ks.
11:199
1 step
12:0
Shutdown delay adjustable from 0 to
to
25,472 Ks.
12:199
1 step
13:0
Without shutdown differential
13:1
Shutdown differential adjustable
to
from 1 to 20 K.
13:20
16:0
Offset adjustable from 0 to 15 K.
to
16:15
17:0
Setting subject to adaptation of mod-
to
ulating burner to the boiler type from
17:255
0 to 25.5 %/K
1 step
18:1
Setting subject to adaptation of mod-
to
ulating burner to the boiler type from
18:199
10 to 1990 s
1 step
1A:0
Duration adjustable from 0 to
to
60 min.
1A:60
1C:1
Delay adjustable from 1 to 199 s.
to
This time is deducted from the oper-
1C:199
ating time at every burner start.
E.g. operating situations where the
burner is shut down via the mechan-
ical temperature controller, but a
burner demand is still present (hours
run continue to be counted).
If required, change the coding ad-
dress "06" in this group.
1F:1
When the limit for the flue gas tem-
to
perature is exceeded, "Service" is
1F:250 °C
displayed.
21:1
The number of hours run before the
to
burner should be serviced, adjusta-
21:100
ble from 100 to 10,000 h.
Coding level 2
128 Ks
128 Ks
128 Ks
0.1 %/K
10 s
45