Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 48

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

Coding level 2
"Solar" group
(cont.)
Coding in the delivered condition
01:4
Stop temperature differential for
solar circuit pump 4 K
02:0
Solar circuit pump is not speed-
controlled
03:10
Temperature differential for the
start of speed control 10 K
04:4
Controller amplification of the
speed control 4 %/K
05:10
Min. speed of the solar circuit
pump 10 % of the max. speed.
06:75
Maximum speed of the solar circuit
pump 75 % of maximum possible
speed
07:0
Interval function of the solar circuit
pump switched off
08:60
Set DHW temperature (maximum
cylinder temperature) 60 °C
09:130
Maximum collector temperature (to
protect system components)
130 °C
0b:0
Frost protection function for solar
circuit switched off
0C:1
Delta T monitoring enabled
No flow rate captured in the solar
circuit, or flow rate too low.
0d:1
Night-time DHW circulation moni-
toring enabled
Unintentional flow in the solar cir-
cuit is captured (e.g. at night).
0E:1
Heat statement in conjunction with
Viessmann heat transfer medium
0F:70
Solar circuit flow rate at maximum
pump speed 7 l/min
0 A:5
Temperature differential for stagna-
tion time reduction (reduction in
the speed of the solar circuit pump
to protect system components and
heat transfer medium) 5 K
48
Possible change
00:30
01:1
Stop temperature differential adjust-
to
able from 1 to 29 K
01:29
02:1
Solar circuit pump is speed-control-
led with wave packet control
02:2
Solar circuit pump is speed-control-
led with PWM control
03:5
Temperature differential adjustable
to
from 5 to 20 K
03:20
04:1
Controller amplification adjustable
to
from 1 to 10 %/K
04:10
05:2
Min. speed of the solar circuit pump
to
adjustable from 2 to 100 %.
05:100
06:1
Max. speed of the solar circuit pump
to
adjustable from 1 to 100 %.
06:100
07:1
Interval function of the solar circuit
pump switched on.
To capture the collector temperature
more accurately, the solar circuit
pump periodically starts for a short
duration.
08:10
Set DHW temperature adjustable
to
from 10 to 90 °C.
08:90
09:20
Temperature adjustable from 20 to
to
200 °C.
09:200
0b:1
Frost protection function for solar cir-
cuit switched on (not required with
Viessmann heat transfer medium)
0C:0
Delta T monitoring disabled
0d:0
Night-time DHW circulation monitor-
ing disabled
0E:2
Do not adjust
0E:0
No heat statement
0F:1
Flow rate adjustable from 0.1 to
to
25.5 l/min.
0F:255
1 step
0 A:0
Stagnation time reduction is disa-
bled.
0 A:1
Temperature differential adjustable
to
from 1 to 40 K.
0 A:40
0.1 l/min