Dhw" Group; Coding - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

Coding level 2
"Boiler" group
(cont.)
Coding in the delivered condition
23:0
No interval for burner service
24:0
No "Service" indication on the dis-
play
26:0
Burner fuel consumption (stage 1):
No count if "26:0" and "27:0" are
programmed.
27:0
Burner fuel consumption (stage 1):
No count if "26:0" and "27:0" are
programmed.
28:0
No burner interval ignition
29:0
Burner fuel consumption (stage 2)
No count if "29:0" and "2A:0" are
programmed.
2A:0
Burner fuel consumption (stage 2).
No count if "29:0" and "2A:0" are
programmed.

"DHW" group

Coding

Coding in the delivered condition
55:0
Cylinder heating
hysteresis
56:0
Set DHW temperature adjustable
from 10 to 60 °C
58:0
Without auxiliary function for DHW
heating
46
2.5 K
±
Possible change
1 step
23:1
Interval adjustable from 1 to 24
to
months.
23:24
24:1
"Service" indicator is shown on the
display (the address is automatically
set and must be manually reset after
a service has been carried out).
26:1
Input from 0.1 to 9.9
to
1 step
26:99
Note
Values of coding addresses "26" and
"27" are added together.
27:1
Input from 10 to 1990
to
1 step
27:199
28:1
Time interval adjustable from 1 to
to
24 h. Burner is force-started once
28:24
every 30 s.
29:1
Input from 0.1 to 9.9
to
1 step
29:99
Note
Values of coding addresses "29" and
"2A" are added together.
2A:1
Input from 10 to 1990
to
1 step
2A:199
Possible change
55:1
Adaptive cylinder heating (see
page 83)
56:1
Set DHW temperature adjustable
from 10 to above 60 °C
Note
Observe the maximum permissible
DHW temperature.
Change over temperature controller
" ".
58:10
Input of a 2nd set DHW tempera-
to
ture, adjustable from 10 to 90 °C
58:60
(observe coding address "56" in this
group)
100 h
0.1 l/h or gallons/h
10 l/h or gallons/h
0.1 l/h or gallons/h
10 l/h or gallons/h