Inserting Cables/Leads And Applying Strain Relief; Connecting The Sensors; Fitting And Connecting An Outside Temperature Sensor - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

Electrical connections
Overview of electrical connections
Plug
fA
lH
X12

Inserting cables/leads and applying strain relief

Blank off unnecessary apertures in the lower part of
the control unit with cable grommets (not cut out).
Cable with cast-on cable entry
2.

Connecting the sensors

Low voltage connections at the PCB (see page 15)
Plug
!
§
%
)
aG

Fitting and connecting an outside temperature sensor

Fitting location for outside temperature sensor
North or north-westerly wall, 2 to 2.5 m above
ground level; in multi storey buildings, in the upper
half of the second floor.
Not above windows, doors or ventilation outlets.
Not immediately below balconies or gutters.
Never render over.
16
(cont.)
Component
Burner
Power supply for accessories
External burner start, stage 1
3.
1.
Component
Outside temperature sensor/radio clock receiver (accessories)
Boiler water temperature sensor
Cylinder temperature sensor
Buffer temperature sensor (accessories)
Flue gas temperature sensor (accessories)
Cable without cast-on cable entry
1.
2.
Outside temperature sensor connection
2-core lead, length up to 35 m with a cross-section of
2
1.5 mm

Hide quick links: